9
|
Electrical installation
Installer reference guide
109
ERGA04~08EAV3(A) + EHBH/X04+08EA/EJ6V+9W
Daikin Altherma 3 R W
4P629085-1 – 2020.08
9.3.2 To connect the backup heater power supply
Backup heater type
Power supply
Wires
*6V
1N~ 230 V (6V)
2+GND
3~ 230 V (6T1)
3+GND
*9W
3N~ 400 V
4+GND
[9.3]
Backup heater
WARNING
The backup heater MUST have a dedicated power supply and MUST be protected by
the safety devices required by the applicable legislation.
CAUTION
If the indoor unit has a tank with a built‑in electrical booster heater, use a dedicated
power circuit for the backup heater and booster heater. NEVER use a power circuit
shared by another appliance. This power circuit must be protected with the required
safety devices according to the applicable legislation.
CAUTION
To guarantee the unit is completely earthed, always connect the backup heater
power supply and the earth cable.
The backup heater capacity can vary, depending on the indoor unit model. Make
sure that the power supply is in accordance with the backup heater capacity, as
listed in the table below.
Backup heater
type
Backup
heater
capacity
Power supply
Maximum
running current
Z
max
*6V
2 kW
1N~ 230 V
(a)
9 A
—
4 kW
1N~ 230 V
(a)
17 A
(b)(c)
0.22 Ω
6 kW
1N~ 230 V
(a)
26 A
(b)(c)
0.22 Ω
2 kW
3~ 230 V
(d)
5 A
—
4 kW
3~ 230 V
(d)
10 A
—
6 kW
3~ 230 V
(d)
15 A
—
*9W
3 kW
3N~ 400 V
4 A
—
6 kW
3N~ 400 V
9 A
—
9 kW
3N~ 400 V
13 A
—
(a)
6V
(b)
Electrical equipment complying with EN/IEC 61000-3-12 (European/International Technical
Standard setting the limits for harmonic currents produced by equipment connected to
public low-voltage systems with input current >16 A and ≤75 A per phase).
(c)
This equipment complies with EN/IEC 61000‑3‑11 (European/International Technical
Standard setting the limits for voltage changes, voltage fluctuations and flicker in public
low-voltage supply systems for equipment with rated current ≤75 A) provided that the
system impedance Z
sys
is less than or equal to Z
max
at the interface point between the user's
supply and the public system. It is the responsibility of the installer or user of the
equipment to ensure, by consultation with the distribution network operator if necessary,
that the equipment is connected only to a supply with a system impedance Z
sys
less than or
equal to Z
max
.
Содержание ERGA04EAV3A
Страница 263: ...11 11...
Страница 264: ...4P629085 1 2020 08 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...