Cooling capacity control
The compressors are factory-equipped with a stepless cooling capacity control system.
Unloading slides
reduces the groove’s intake capacity and reduces its actual length.
Unloading slides are controlled by the pressure of the oil coming from the separator or drained towards the compressor
suction; springs acts for producing the forces for moving the slide.
The oil flow is controlled by solenoid valves, according to inputs from the unit controller.
Fr3100 compressor, having one satellite, has one slide only, while F3 compressors have two unloding slides. The first
slide allows to change the load continuously while the second one has on/off operation.
Figure 30 - Capacity control mechanism for Fr3100 compressor
Figure 31 - Capacity control mechanism for F3 compressor
Load
(50%)
Unload
(0%)
Unoad
(12.5%)
Load
(50%)
Modulating slide
On/OFF Slide
Oil supply
Gas supply
Drainage to suction
Drainage to suction
Oil supply
Spring
Slide
Oil Vent to Suction
A
NC
B
NC
Oil Supply
Discharge pressure acts
on this side of piston
Load
Unload
Содержание ERAD 120E-SL