2
Technical data
Operating voltage:
230 V ±10 %, 50 Hz
Fuse 230 V:
T2AH
Switching elem. 230 V:
Relay
Switching power 230 V:
2 A resist. load
Rated current w/o valve drives:
230 V: ≤2 mA
Max current draw allowed
with connected valve drives:
230 V: 1.8 A
Temperature setting range:
10 °C - 28 °C
Target value calibration:
±2 K
Reduction temperature:
2 K
Temperature measurement:
0 - 40 °C
Measuring accuracy:
±0.5 K
Ambient temperature:
0 - 50 °C
Storage temp. range:
-25 to +75 °C
Admissible amb. humidity:
80%, not condensing
Temp. for ball pressure test:
Terminals: 100 °C
Plastic enclosure: 75 °C
CE conformity according to:
EN 60730
Protect. class 230 V:
II
Protection degree:
IP 20
Rated impulse voltage:
1500 V
Pollution degree:
2
Type action:
Type 1 / Type 1.C
Weight:
90 g
Dimensions (W x H x D):
86 x 86 x 29 mm
Antifreeze function: From +6 °C in heating mode, inactive in cooling mode.
Only thermostats with heating/cooling function:
Valve protection function: Once every 14 days for 6 minutes after the last
activation
4P560991-1
2019.01
Copyright 2019 Daikin
This symbol means that electrical and electronic products may
NOT be mixed with unsorted household waste. Units must be
treated at a specialized treatment facility for reuse, recycling
and recovery.
By ensuring this product is disposed of correctly, you will help
to prevent potential negative consequences for the environment
and human health.
For more information, contact your installer or local authority.