background image

 

EK18
4PW34861-1A

 

1

 

I

 

NTRODUCTION

 

This kit is an obligatory option especially designed for ensuring
optimum operation of the system in case the outdoor unit is installed
between 50 and 90 m above the lowest indoor unit.

 

C

 

ONTENT

 

 

 

OF

 

 

 

THE

 

 

 

KIT

 

The kit includes all necessary parts and instructions for building the
difference in height installation kit into the outdoor unit. See 

figure 1

.

 

N

 

ECESSARY

 

 

 

TOOLS

 

 

 

FOR

 

 

 

PROCESSING

 

I

 

NSTALLATION

 

 

 

PROCEDURE

 

Follow procedure steps as visualized in figures and as listed in table
below.

 

I

 

MPACT

 

 

 

OF

 

 

 

THIS

 

 

 

KIT

 

 

 

ON

 

 

 

STANDARD

 

 

 

INSTALLATION

 

 

 

PROCEDURES

 

The obligatory installation of this kit has no impact on:

 

 

Connection ratio of total allowed indoor unit capacity;

 

 

Equivalent pipe length between outdoor and indoor units;

 

 

Automatic charging of refrigerant;

 

 

Leak detection function;

 

 

Indoor unit installation conditions and the required field settings
resulting from these conditions.

 

N

 

OTES

 

EKLD90P12
EKLD90P18

 

Difference in height installation kit up to 90 m

 

Instruction manual

 

EKLD90P12

EKLD90P18

1

 

Brazing equipment

Brazing equipment

 

2

 

Wire cutter

Wire cutter

 

3

 

Pipe cutter

 

Make sure to permanently cool the liquid stop valve when
brazing.

 

EKLD90P12

EKLD90P18

 

See 

figure 2

.

See 

figure 3

.

 

1

 

Braze the standard installed 
pinched pipe loose from the 
tube that is brazed to the liquid 
side stop valve.

 

1

 

Cut the standard installed liquid 
pipe at the specified length 
beneath the liquid side stop 
valve as indicated in the 
illustration.

 

2

 

Position the option kit behind the compressor as indicated in the 
illustration.

 

3

 

Match the pipe-end at the 
position where the pinched pipe 
was brazed loose.

 

3

 

Match the pipe-end at the 
position where the liquid pipe 
was cut.

 

4

 

Match the non-return check valve (insulated part) and filter part of the 
option kit against the insulation on the 2-way suction pipe behind the 
compressor.
Fix the option part (both the non-return check valve and the filter 
together) against the insulation on the 2-way suction pipe by firmly 
strapping the 2 parts with the supplied tie-wrap as illustrated.

 

5

 

Perform brazing of the option kit.

 

Installation of this kit requires that the size of the main
liquid pipe be increased.