8 Commissioning

Installation manual

19

E120B
R32 Split series – Domestic hot water tank
4P680074-1C – 2022.11

8

Commissioning

NOTICE

General 

commissioning 

checklist.

 

Next 

to 

the

commissioning  instructions  in  this  chapter,  a  general
commissioning  checklist  is  also  available  on  the  Daikin
Business Portal (authentication required).

The  general  commissioning  checklist  is  complementary  to
the  instructions  in  this  chapter  and  can  be  used  as  a
guideline and reporting template during commissioning and
hand-over to the user.

NOTICE

ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.

INFORMATION

Protective  functions  –  "Installer-on-site  mode"

.  The

software  is  equipped  with  protective  functions,  such  as
tank  disinfection.  The  unit  automatically  runs  these
functions when necessary.

During  installation  or  service  this  behaviour  is  undesired.
Therefore, the protective functions can be disabled:

At  first  power-on:

  The  protective  functions  are

disabled  by  default.  After  36  hours  they  will  be
automatically enabled.

Afterwards:

  An  installer  can  manually  disable  the

protective  functions  by  setting  [9.G]: 

Disable

protections

=

Yes

.  After  his  work  is  done,  he  can

enable  the  protective  functions  by  setting  [9.G]:

Disable protections

=

No

.

Also see 

"Protective functions"

 [

4

 14].

8.1

Checklist before commissioning

1

After the installation of the unit, check the items listed below.

2

Close the unit.

3

Power up the unit.

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

indoor unit

 is properly mounted.

The 

outdoor unit

 is properly mounted.

The following 

field wiring

 has been carried out according

to this document and the applicable legislation:

▪ Between the local supply panel and the outdoor unit

▪ Between indoor unit and outdoor unit

▪ Between the local supply panel and the indoor unit

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed according to this document, and have NOT been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

Booster  heater  circuit  breaker

  F2B  (field  supply)  is

turned ON.

There are NO 

refrigerant leaks

.

The 

refrigerant  pipes

  (gas  and  liquid)  are  thermally

insulated.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

There is NO 

water leak

 inside the indoor unit.

The 

stop  valves

  (gas  and  liquid)  on  the  outdoor  and

indoor units are fully open.

The 

domestic hot water tank

 is filled completely.

8.2

Checklist during commissioning

To perform a 

test run

.

To perform an 

actuator test run

.

8.2.1

To perform an operation test run

Conditions: 

Make  sure  all  operation  is  disabled.  Go  to  [C]:

Operation

 and turn off 

Tank

 operation.

1

Set the user permission level to 

Installer

. See 

"To

change the user permission level"

 [

4

 13].

2

Go to [A.1]: 

Commissioning

 > 

Operation test

run

.

3

Select the 

Tank

..

4

Select 

OK

 to confirm.

Result: 

The test run starts. It stops automatically

when ready (±30 min).

To stop the test run manually:

1

In the menu, go to 

Stop test run

.

2

Select 

OK

 to confirm.

INFORMATION

If  the  outdoor  temperature  is  outside  the  range  of
operation,  the  unit  may  NOT  operate  or  may  NOT  deliver
the required capacity.

To monitor tank temperatures

During test run, the correct operation of the unit can be checked by
monitoring its tank temperature (domestic hot water mode).

To monitor the temperatures:

1

In the menu, go to 

Sensors

.

2

Select the temperature information.

8.2.2

To perform an actuator test run

Purpose

Perform an actuator test run to confirm the operation of the different
actuators.  For  example,  when  you  select 

Booster  heater

,  a  test

run of the booster heater will start.

Conditions: 

Make  sure  all  operation  is  disabled.  Go  to  [C]:

Operation

 and turn off 

Tank

 operation.

1

Set the user permission level to Installer. See 

"To

change the user permission level"

 [

4

 13].

2

Go to [A.2]: 

Commissioning

 > 

Actuator test run

.

3

Select 

Booster heater

.

Содержание EKHWET90B V3 Series

Страница 1: ...llation manual R32 Split series Domestic hot water tank English Installation manual R32 Split series Domestic hot water tank EKHWET90B V3 EKHWET120B V3 1 2 3 9 A B C Z 1 2 3 9 https daikintechnicaldatahub eu ...

Страница 2: ...тите се използват в съответствие с нашите инструкции atitinka toliau nurodytas direktyvas arba reglamentus su sąlyga kad gaminiai bus eksploatuojami laikantis mūsų instrukcijų atbilst šādām direktīvām vai regulām ja vien šie izstrādājumi tiek lietoti saskaņā ar mūsu instrukcijām sú v zhode s nasledujúcou imi smernicou ami alebo predpisom mi za predpokladu že sa výrobky používajú v zhode s našimi p...

Страница 3: ...uator test run 19 9 Hand over to the user 20 10 Technical data 21 10 1 Piping diagram Indoor unit 21 10 2 Wiring diagram Indoor unit 22 1 About this document Target audience Authorised installers Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read before installing Format Paper in the box of t...

Страница 4: ...ing the indoor unit 410 WARNING Fixing method of the indoor unit MUST be in accordance with the instructions from this manual See 4 3 Mounting the indoor unit 410 Piping installation see 5 Piping installation 410 WARNING The field piping method MUST be in accordance with the instructions from this manual See 5 Piping installation 410 Electrical installation see 6 Electrical installation 411 DANGER...

Страница 5: ...for the following ambient temperatures Domestic hot water production 5 35 C Mind the following spacing installation guidelines 300 300 300 300 400 mm 300 300 Additionally to the spacing guidelines Because the total refrigerant charge in the system is 1 84 kg the room where you install the indoor unit must also comply with the conditions described in 4 1 3 Installation patterns 46 4 1 2 Special req...

Страница 6: ...ease height From floor to 100 mm below top of the unit N A Not applicable Minimum floor area Release height The minimum floor area requirements depend on the release height of the refrigerant in case of a leakage The higher the release height the lower the minimum floor area requirements The default point of release is 100 mm below the top of the unit You can also take advantage of the floor area ...

Страница 7: ...d Must be 50 of Anv min minimum bottom opening area Must be 1 5 m from the floor A B Anv Anv min Min 50 of Anv min Calculate the total floor area Atotal AroomA AroomB See table 4 Look up the minimum bottom opening area for natural ventilation with the adjacent room Anv min for the given refrigerant charge the given floor area of room A AroomA NOT room A room B and the given release height H1 Is it...

Страница 8: ...32 2 71 1 84 1 59 1 43 2 5 5 53 2 82 1 91 1 65 1 49 1 37 2 6 5 75 2 93 1 99 1 71 1 54 1 42 Table 3 Minimum bottom opening area for natural ventilation Take the following into account Use the correct table For intermediate refrigerant charges use the table with the higher value Example If the refrigerant charge is 2 34 kg use the table of 2 4 kg For intermediate floor areas use the column with the ...

Страница 9: ...ust be 200 mm from the floor of the unoccupied room The bottom of the opening must be 100 mm from the floor of the unoccupied room If the opening starts from the floor the height of the opening must be 20 mm a2 Top opening for natural ventilation between room A and the outside Must be a permanent opening that cannot be closed Must be 50 of Anv min minimum bottom opening area as specified in the ta...

Страница 10: ...nds without brazing If brazing should be needed take the guidelines in the outdoor unit installer reference guide into account Also see 4 1 2 Special requirements for R32 units 4 5 for additional requirements For information related with piping length diameter connections and insulation see the Installation manual Outdoor unit 5 2 Connecting refrigerant piping See the installation manual of the ou...

Страница 11: ... to the indoor unit a b a DHW hot water OUT screw connection b DHW cold water IN screw connection 2 Install the following components field supply on the cold water inlet of the DHW tank h d b a e c f g c a DHW hot water OUT screw connection b DHW cold water IN screw connection c Shut off valve recommended d Non return valve recommended e Pressure reducing valve recommended f Pressure relief valve ...

Страница 12: ...To connect the main power supply 1 Open the following see 4 2 1 To open the indoor unit 49 2 Connect the main power supply Interconnection cable main power supply Wires 3 GND 1 5 mm a 1 2 3 A A a Interconnection cable main power supply B B C C D D X2M 6 3 2 To connect the booster heater power supply Booster heater cable Wires 2 GND 1 5 mm 9 4 Booster heater WARNING The booster heater MUST have a d...

Страница 13: ...ration wizard starts to help you configure the system Restart the configuration wizard If the system is already configured you can restart the configuration wizard To restart the configuration wizard go to Installer settings Configuration wizard To access Installer settings see 7 1 1 To access the most used commands 413 Afterwards If necessary you can make changes to the configuration in the menu ...

Страница 14: ...n the left dial to select the second part of the setting 00 01 23 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 2 5 Turn the right dial to modify the value from 23 to 3 00 01 3 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 2 6 Press the left dial to confirm the new setting 7 Press the center button to go back to the home screen INFORMATION When you change the overview settings and you go back to the home screen...

Страница 15: ...eheat operation is allowed 2 Schedule only The domestic hot water tank can ONLY be heated according to a schedule See the operation manual for more details Settings for Reheat only mode During Reheat only mode the tank setpoint can be set on the user interface The maximum allowed temperature is determined by the following setting Code Description 5 8 6 0E Maximum The maximum temperature that users...

Страница 16: ...hich type of curve you use to make adjustments depends on your personal preference See 7 3 4 Using weather dependent curves 417 Availability The weather dependent curve is available for Tank only available to installers INFORMATION To operate weather dependent correctly configure the setpoint of the tank See 7 3 4 Using weather dependent curves 417 7 3 2 2 points curve Define the weather dependent...

Страница 17: ... WD curve type Restriction Only available to installers To change the weather dependent curve Zone Go to Tank Restriction Only available to installers 5 C Tank WD curve INFORMATION Maximum and minimum setpoints You cannot configure the curve with temperatures that are higher or lower than the set maximum and minimum setpoints for the tank When the maximum or minimum setpoint is reached the curve f...

Страница 18: ...mergency Power consumption control Auto restart Power saving function Disable protections Overview field settings 9 4 Booster heater Capacity Quick mode timer Operation Export MMI settings 9 9 Power consumption control Power consumption control Type Limit Priority heater 9 5 Emergency Emergency Can NOT be adjusted INFORMATION Depending on the selected installer settings and unit type settings will...

Страница 19: ... installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matches the voltage on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units Booster heater circuit breaker F2B fiel...

Страница 20: ...s finished and the unit operates properly make sure the following is clear for the user Fill in the installer setting table in the operation manual with the actual settings Make sure that the user has the printed documentation and ask him her to keep it for future reference Inform the user that he can find the complete documentation at the URL mentioned earlier in this manual Explain the user how ...

Страница 21: ...aikin website publicly accessible The full set of latest technical data is available on the Daikin Business Portal authentication required 10 1 Piping diagram Indoor unit R5T a1 c a2 R3T b1 b2 3D138207 a1 Domestic hot water hot water out Thermistors a2 Domestic hot water cold water in R3T Thermistor heat exchanger Liquid pipe b1 Liquid stop valve R5T Tank thermistor b2 Gas stop valve c Booster hea...

Страница 22: ...k switch box Multi domestic hot water tank switch box Indoor Indoor Outdoor Outdoor SWB Switch box 2 Legend 2 Legend A1P Main PCB F2B Overcurrent fuse booster heater FU1 A1P fuse 5 A 250 V for PCB K3M Contactor booster heater Q1DI Earth leakage circuit breaker TR1 Power supply transformer X4M Booster heater power supply terminal strip client X8M Booster heater power supply terminal strip X X A X B...

Страница 23: ...wiring Power supply OUTDOOR UNIT X5M 1 2 3 earth 4 core X2M 1 2 3 earth INDOOR UNIT 1 1 booster heater power supply 1 2 kW 230 V earth STANDARD PART X1M L N earth Only for normal power supply installation unit power supply 230 V earth Only for preferential kWh rate power supply installation unit preferential kWh rate power supply 230 V earth X8M L N earth F2B 3 core 3 core 3 core X4M ...

Страница 24: ...4P680074 1C 2022 11 Copyright 2021 Daikin 4P680074 1 C 0000000 Verantwortung für Energie und Umwelt ...

Отзывы: