EKHBH/X016BB
Indoor unit for air to water heat pump system
4PW62572-1A – 01.2011
Installation manual
38
[F] Option setup
Pump operation
The pump operation field setting apply to the pump operation logic
only when DIP switch SS2-3 is OFF.
When the pump operation function is disabled the pump will stop if
the outdoor temperature is higher than the value set by [4-02] or if the
outdoor temperature drops below the value set by [F-01]. When the
pump operation is enabled, the pump operation is possible at all
outdoor temperatures. Refer to
"8.3. Pump operation configuration"
.
■
[F-00] Pump operation: specifies wether the pump operation
function is enabled (1) or disabled (0).
Space cooling permission
■
[F-01] Space cooling permission temperature: defines the
outdoor temperature below which space cooling is turned off.
Bottom plate heater control
Applies only to installation with an outdoor unit ERLQ or in case the
option bottom plate heater kit is installed.
■
[F-02] Bottom plate heater ON temperature: defines the
outdoor temperature below which the bottom plate heater will
be activated by indoor unit in order to prevent ice build-up in
the bottom plate of the outdoor unit at lower outdoor
temperatures.
■
[F-03]
Bottom plate heater hysteresis: defines the
temperature difference between bottom plate heater ON
temperature and the bottom plate heater OFF temperature.
Bottom plate heater
T
A
Outdoor temperature
Functionality of X14A
■
[F-04] Functionality of X14A: specifies if the logic of X14A
follows the output signal for the solar kit model (EKSOLHW)
EKHBH/X_AA/AB (0) or if the logic of X14A follows the
output for the bottom plate heater (1).
INFORMATION
This function is only valid for EKHBX when space
cooling is selected.
CAUTION
The bottom plate heater is controlled via X14A. Make sure
[F-04] is correctly set.
INFORMATION
The bottom plate heater at ERLQ_CA is controlled
internally by the outdoor unit pcb. The field settings [F-02]
and [F-03] are not applicable for this unit.
T
A
[F-02]
[F-03]
ON
OFF
INFORMATION
Independent from field setting [F-04], the contact X3-X4
(EKRP1HB) follows the logic of the output signal for the
solar kit model (EKSOLHW). See figure below for the
schematic location of this contact.
YC Y1 Y2 Y3 Y4
X1
X2
X3
X4
OFF ON
X2M
SS1
X1M
Содержание EKHBH016BB3V3
Страница 54: ......
Страница 55: ......
Страница 56: ...4PW62572 1A 01 2011 Copyright 2010 Daikin ...