111
Part 4 Troubleshooting
4
3
4
5
4
4.5
E7
Malfunction of Outdoor Unit Fan Motor
Remote controller
display
E7
Method of
malfunction
detection
Abnormality of fan motor system is detected according to the fan speed detected by hall IC when the
fan motor runs.
Malfunction
decision conditions
When the fan runs with speed less than a specified one for 15 seconds or more when the fan motor
running conditions are met
When connector detecting fan speed is disconnected
When malfunction is generated 4 times, the system shuts down.
Supposed causes
Malfunction of fan motor
The harness connector between fan motor and PC board is left in disconnected, or faulty connector
Fan does not run due to foreign matters tangled
Malfunction of the outdoor (inverter) PC board
Blowout of fuse
Содержание EHYHBH05AAV3
Страница 16: ...Introduction ESIE13 02A 16 3 1 4 5...
Страница 29: ...ESIE13 02A Functionality 29 Part 1 System Outline 3 1 4 5...
Страница 30: ...Functionality ESIE13 02A Part 1 System Outline 30 3 1 1 4 5...
Страница 35: ...ESIE13 02A Wiring Diagrams 35 Part 1 System Outline 3 1 4 5...
Страница 36: ...Wiring Diagrams ESIE13 02A Part 1 System Outline 36 3 1 1 4 5...
Страница 38: ...Wiring Diagrams ESIE13 02A Part 1 System Outline 38 3 1 1 4 5 3 3 Cable Dimensions...
Страница 39: ...ESIE13 02A Wiring Diagrams 39 Part 1 System Outline 3 1 4 5...
Страница 50: ...Outdoor Unit ESIE13 02A Part 2 Specifications 50 3 1 2 5...
Страница 51: ...ESIE13 02A 51 Part 3 Commissioning 4 3 4 5 3 Part 3 Commissioning See Note on page 6...
Страница 52: ...ESIE13 02A Part 3 Commissioning 52 3 1 3 5...
Страница 98: ...Error Codes Hydro box ESIE13 02A Part 4 Troubleshooting 98 3 1 4 5 Troubleshooting...
Страница 115: ...ESIE13 02A Error Codes Outdoor Units 115 Part 4 Troubleshooting 4 3 4 5 4 Troubleshooting...
Страница 166: ...Tips and Tricks ESIE13 02A Part 5 Repair 166 3 1 5 5 1 Tips and Tricks Not available at this moment...
Страница 170: ...Maintenance Schedule ESIE13 02A Part 6 Maintenance 170 3 1 6...