3 Installation
Installation manual
7
EHBH/X04~16CA
Daikin Altherma - Low Temperature Split
4P313771-1C – 2012.11
3.4.4
To insulate the water piping
The piping in the complete water circuit must be insulated to prevent
condensation during cooling operation and reduction of the heating
and cooling capacity.
If the temperature is higher than 30°C and the humidity is higher
than RH 80%, the thickness of the sealing materials should be at
least 20 mm to prevent condensation on the surface of the sealing.
3.5
Connecting the electrical wiring
DANGER: RISK OF ELECTROCUTION
WARNING
Always use multicore cable for power supply cables.
3.5.1
About electrical compliance
See "3.5.4 To connect the backup heater power supply" on
page 8.
3.5.2
To connect the electrical wiring on the
indoor unit
1
To open the indoor unit, see "3.1.1 To open the indoor unit" on
page 4.
2
Wiring should enter the unit from the bottom.
3
Routing of the wiring inside the unit should be as follows:
For EHBH/X04+08:
a
b
c
a
b
c
For EHBH/X16:
a
c
b
a
c
c
c
b
INFORMATION
When installing field supply or option cables, foresee
sufficient cable length. This will make it possible to remove/
reposition the switch box and gain acces to other
components during service.
Routing
Possible cables (depending on unit type and installed options)
a
Low voltage
▪ User interface
▪ Domestic hot water tank thermistor (option)
▪ Power consumption digital inputs (field supply)
▪ Outdoor ambient temperature sensor (option)
▪ Indoor ambient temperature sensor (option)
▪ Electrical meters (field supply)
b
High voltage power supply
▪ Interconnection cable
▪ Normal kWh rate power supply
▪ Preferential kWh rate power supply
▪ Power supply for backup heater
▪ Power supply for bottom plate heater (option)
▪ Power supply for booster heater (to indoor unit)
▪ Power supply for booster heater and thermal protection (from indoor unit)
Содержание EHBH04CA
Страница 25: ...Notes_1 fm Page 1 Tuesday December 4 2012 2 51 PM ...
Страница 26: ...Notes_1 fm Page 1 Tuesday December 4 2012 2 51 PM ...
Страница 27: ...Notes_1 fm Page 1 Tuesday December 4 2012 2 51 PM ...
Страница 28: ...4P313771 1C 2012 11 Copyright 2012 Daikin ...