4 Configuration
Installation manual
13
EHBH/X04~16CA
Daikin Altherma - Low Temperature Split
4P313771-1C – 2012.11
4.2
Basic configuration
4.2.1
Quick wizard: Language / time and date
#
Code
Description
[A.1]
N/A
Language
[1]
N/A
Time and date
4.2.2
Quick wizard: Standard
Backup heater configuration
#
Code
Description
[A.2.1.5]
[5-0D]
Backup heater type:
▪ 1 (1P,(1/1+2)): 6 kW 1~ 230 V (*9W)
▪ 3 (3P,(1/1+2)): 6 kW 3~ 230 V (*9W)
▪ 4 (3PN,(1/2)): 6 kW 3N~ 400 V (*9W)
▪ 5 (3PN,(1/1+2)): 9 kW 3N~ 400 V
(*9W)
Space heating/cooling settings
#
Code
Description
[A.2.1.7]
[C-07]
Unit temperature control:
▪ 0 (LWT control): Unit operation is
decided based on the leaving water
temperature.
▪ 1 (Ext RT control): Unit operation is
decided by the external thermostat.
▪ 2 (RT control): Unit operation is
decided based on the ambient
temperature of the user interface.
[A.2.1.B]
N/A
Only if there are 2 user interfaces:
User interface location:
▪ At unit
▪ In room
[A.2.1.8]
[7-02]
Number of water temperature zones:
▪ 0 (1 LWT zone): Main
▪ 1 (2 LWT zones): Main + additional
[A.2.1.9]
[F-0D]
Pump operation:
▪ 0 (Continuous): Continuous pump
operation, regardless of thermo ON or
OFF condition.
▪ 1 (Sample): When thermo OFF
condition occurs, the pump runs every
5 minutes and the water temperature
is checked. If the water temperature is
below target, unit operation can start.
▪ 2 (Request): Pump operation based
on request. Example: Using a room
thermostat and thermostat creates
thermo ON/OFF condition.
4.2.3
Quick wizard: Options
Domestic hot water settings
#
Code
Description
[A.2.2.1]
[E-05]
Domestic hot water tank:
▪ 0 (No): NOT installed
▪ 1 (Yes): Installed
#
Code
Description
[A.2.2.3]
[E-07]
Tank booster heater:
▪ 0 (Horizontal BSH): Installed at side of
the tank
▪ 1 (Backup heater): NOT installed
▪ 2: N/A
▪ 3: N/A
[A.2.2.A]
[D-02]
Domestic hot water pump:
▪ 0 (No): NOT installed
▪ 1 (Secondary rtrn): Installed for instant
hot water
▪ 2
(Disinf.
shunt):
Installed
for
disinfection
See also illustrations below.
Domestic hot water pump installed for…
Instant hot water
Disinfection
c
f
b
a
g
c
b
a
d
f
e
g
a
Indoor unit
b
Tank
c
Domestic hot water pump
d
Heater element
e
Non
‑
return valve
f
Shower
g
Cold water
Thermostats
#
Code
Description
[A.2.2.4]
[C-05]
External room thermostat for the
main
zone:
▪ 1 (Thermo ON/OFF): When the used
external
room
thermostat
or
heat pump convector can only send a
thermo
ON/OFF
condition.
No
separation between heating or cooling
demand.
▪ 2 (C/H request): When the used
external room thermostat can send a
separate
heating/cooling
thermo
ON/OFF condition.
[A.2.2.5]
[C-06]
External room thermostat for the
additional
zone:
▪ 0: N/A
▪ 1 (Thermo ON/OFF): When the used
external
room
thermostat
or
heat pump convector can only send a
thermo
ON/OFF
condition.
No
separation between heating or cooling
demand.
▪ 2 (C/H request): When the used
external room thermostat can send a
separate
heating/cooling
thermo
ON/OFF condition.
[A.2.2.B]
[C-08]
External sensor:
▪ 0 (No): NOT installed.
▪ 1 (Outdoor sensor): Connected to
PCB
measuring
the
outdoor
temperature.
▪ 2 (Room sensor): Connected to PCB
measuring the indoor temperature.