ESIE13-03
|
Part 2. Troubleshooting
3. Symptom based troubleshooting
Page 46
13/05/15
|
Version 2.0
Ground source heat pump
3.7. Brine leakage
3.8. Power consumption too high
Possible failures
Root cause
Check
Corrective action
Root cause category: installation
Drain connection of brine
safety valve (SV1) leaking.
Bad connection between unit
drain pipe (brine) and field
drain pipe.
Check the drain connection of
the brine safety valve.
Correct the drain connection if
required.
Leakage of drain valve brine
side (DR1, DR2).
Valve not completely closed.
Check if drain valve is closed.
Close the drain valve.
Root cause category: component - mechanical
Safety valve brine side (SV1)
blocked or leaking.
Component failure.
• Check safety valve (see
• Check
water
(brine)
quality.
Replace brine safety valve
(see
).
Leakage of drain valve brine
side (DR1, DR2).
Component failure.
Check drain valve.
Replace brine drain valve.
Broken bellow of brine side
expansion vessel (EXP1).
Component failure.
Check expansion vessel (see
Replace brine expansion ves-
sel (see
).
Expansion vessel (EXP1) not
pressurized.
Component failure.
Check expansion vessel (see
Replace brine expansion ves-
sel (see
).
Possible failures
Root cause
Check
Corrective action
Root cause category: end user
Too high domestic hot water
setpoint.
User set too high domestic hot
water setpoint by schedule or
manual operation.
Check domestic hot water tank
set temperature; avoid electric
heater use.
Adapt domestic hot water set-
point (e.g. 50-55°C).
Too high leaving water temper-
ature setpoint.
User set too high leaving water
temperature setpoint by
schedule or manual operation.
Check leaving water setpoint.
Adapt leaving water setpoint
(e.g. < 55°C will reduce
backup heater operation).
Too high space heating set-
point on room thermostat.
User set too high room set-
point by schedule or manual
operation.
Check room thermostat set-
point.
Adapt room thermostat set-
point.
Root cause category: parameter (setting)
Too high leaving water temper-
ature (LWT) - weather depend-
ent.
Incorrect weather dependent
setting --> too high LWT limit
set [A.3.1.1.3] [A.3.1.2.3].
Check LWT high limit in
weather dependent (setting
[1-03]).
Adapt high LWT limit for
weather dependent heating
(setting [1-03]).
User interface thermostat used
with setting [A.2.1.7] on value
1 (= external thermostat con-
trol).
Wrong setting of [A.2.1.7] -
unit control method.
Check setting [A.2.1.7].
Adjust setting to match appli-
cation - refer to installers refer-
ence guide.
Pump keeps running all the
time during space heating
operation.
Wrong setting of [A.2.1.9] -
pump operation.
Check pump operation mode
setting [F-0D].
Change setting [F-0D] from
continuous operation (value 0)
to Sample (1) or Request (2).
Refer to installer reference
guide for applicable value.
Setting disinfection operation
day [2-00] was set to 0 (each
day).
Setting disinfection operation
day [2-00] was set to 0 (each
day).
Check setting [2-00].
Unit is running in emergency
operation and is using backup
heater only.
[4-06] is set to 1.
Unit is running in emergency
operation and is using backup
heater only.
[4-06] is set to 1.
Check setting [4-06].