Troubleshooting
Service manual
92
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
3.4.11 Symptom: Space heating (cooling) capacity shortage
Root cause category: end user
Possible failure
Root cause
Check
Repair
Space heating: too low
leaving water temperature
setpoint.
Space cooling: too high
leaving water temperature
setpoint.
User set too low (space
heating) or too high (space
cooling) leaving water
temperature setpoint by
schedule or manual
operation.
Check leaving water
setpoint.
Adapt leaving water
setpoint.
(Remark: check the
weather dependent
settings (relation outdoor
temperature - setpoint) in
case weather dependent
control is activated.)
Too low (space heating) or
too high (space cooling)
setpoint on room
thermostat.
User set too low (space
heating) or too high (space
cooling) room setpoint by
schedule or manual
operation.
Check room thermostat
setpoint.
Adapt room thermostat
setpoint.
(Remark: check the
weather dependent
settings (relation outdoor
temperature - setpoint) in
case weather dependent
control is activated.)
Space heating (cooling)
NOT activated.
Check if space heating
(cooling) is activated.
Root cause category: parameter (setting)
Possible failure
Root cause
Check
Repair
External room thermostat
used with setting [C‑07] on
value 2 (= RT control).
Wrong setting of [C‑07] -
unit control method.
Check setting [C‑07].
Adjust setting to match
application - see installer
reference guide.
Backup heater operation
disabled (setting [4‑00] is
set to 0 or 2).
Setting backup heater
operation mode [4‑00] is
set 0 (backup heater
disabled) or 2 (ONLY
domestic hot water).
Check setting [4‑00].
Change setting [4‑00] to 1.
Setting domestic hot water
operation mode [6‑0D]
NOT set optimally.
Setting domestic hot water
operation mode [6‑0D] is
set to 0 (reheat ONLY). This
will cause the system to
work too frequently in
domestic hot water
operation and less in space
heating.
Check setting [6‑0D].
It is advisable to set to
factory setting (
schedule) and program the
schedule to heat the
domestic hot water during
periods of no space
heating required.
Root cause category: installation
Possible failure
Root cause
Check
Repair
3‑way valve does NOT
switch correctly between
space heating (cooling)
connection and domestic
hot water connection.
3‑way valve incorrectly
mounted.
Check the 3‑way valve.
Correct the position of the
3‑way valve.