3
|
Troubleshooting
Service manual
78
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
2
For more information about the configuration and further troubleshooting,
see
the
ONECTA
app
or
see
the
website:
www.onlinecontroller.daikineurope.com/
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.3.89 UA-00 – Indoor unit, outdoor unit mismatching problem
Trigger
Effect
Reset
Signal transmission
between outdoor and
indoor unit abnormality.
Improper combination of
outdoor and indoor unit.
Unit will stop operating.
Power reset via outdoor
unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check the wiring between the hydro PCB and the main PCB. See
254].
Possible cause:
Faulty wiring between the hydro PCB and main PCB.
2
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
3
Perform a check of the hydro PCB. See
Possible cause:
Faulty hydro PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.3.90 UA-17 – Tank type problem
Trigger
Effect
Reset
[E-05] is not set as 1, or
[E-07] is not set correctly.
Unit will stop operating.
Power reset via outdoor
unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check for improper combination of the indoor unit and the water tank. See
the combination table in the Databook for more information.