4
|
Components
Service manual
237
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
To install the user interface
1
See relevant manual of the user interface (remote controller) for the correct
procedure.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To adjust the settings
1
See the relevant documentation (installer reference guide, remote controller
manual, …) to adjust the specific setting.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
To install the software
1
Install the software using the Updater Tool. See the Business Portal (
) for more information about the Updater Tool.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
4.21 Water flow sensor
4.21.1 Checking procedures
To perform an electrical check of the water flow sensor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Turn ON the power of the unit.
2
Activate
Installer
on the user interface. See the installer reference guide
for the correct procedure.
3
Go to
Actuator test run
via the user interface.
4
Activate the
Pump
.
5
Select
Flow rate
.
Result:
The displayed flow rate MUST be 5~60 l/min.
6
Measure the water flow with a calibrated external flow meter.
7
Measure the frequency on connector X34A between pins 2‑3 (= flow sensor
output signal) on the hydro PCB.
draft – 31/05/2022 15:53