SiAU18-715
Troubleshooting for SkyAir Indoor Unit
Troubleshooting
341
5.8
Malfunction of Heat Exchanger Thermistor (R2T)
Remote
Controller
Display
C4
Applicable
Models
FFQ, FCQ, FBQ, FHQ
Method of
Malfunction
Detection
Malfunction detection is carried out by temperature detected by heat exchanger sensor.
Malfunction
Decision
Conditions
When the heat exchanger thermistor becomes disconnected or shorted while the unit is running.
Supposed
Causes
Failure of the sensor itself
Broken or disconnected wire
Failure of electronic circuitry (indoor unit PCB)
Failure of connector contact
Troubleshooting
Check No.02
Refer to P.349
Connect correctly.
Heat exchanger
sensor replacement.
If contact is OK,
replace indoor unit
PCB.
NO
NO
YES
YES
(Q0538)
Disconnect the heat exchanger
sensor (R2T) from X18A on
the indoor unit PCB and
measure the resistance.
Is the
thermistor normal?
(See note)
Is it normal?
Check contact of connector
+
See
Check No. 02
for “Thermistor temperature and resistance characteristics”.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Содержание E Series
Страница 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Страница 26: ...SiAU18 715 Specifications 13 Part 2 Specifications 1 Specifications 14 1 1 Cooling Only 14 1 2 Heat Pump 23 ...
Страница 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Страница 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Страница 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Страница 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Страница 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Страница 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Страница 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Страница 449: ...SiAU18 715 vi Index ...