Troubleshooting for SkyAir Indoor Unit
SiAU18-715
340
Troubleshooting
5.7
Malfunction of Capacity Setting
Remote
Controller
Display
AJ
Applicable
Models
FFQ, FCQ, FBQ, FHQ
Method of
Malfunction
Detection
Capacity is determined according to resistance of the capacity setting adaptor and the memory
inside the IC memory on the indoor unit PCB, and whether the value is normal or abnormal is
determined.
Malfunction
Decision
Conditions
Operation and:
(1)When the capacity code is not contained in the PCB’s memory, and the capacity setting
adaptor is not connected.
(2)When a capacity that doesn’t exist for that unit is set.
Supposed
Causes
Failure of capacity setting adaptor connection
Failure of indoor unit PCB
Troubleshooting
Note:
Capacity is factory set in the data IC on the PCB. A capacity setting adaptor that matches the
capacity of the unit is required in the following case.
If the indoor PCB installed at the factory is for some reason changed at the installation site, the
capacity will not be contained in the replacement PCB.
If you connect a capacity setting adaptor to a PCB in which the capacity is memorized, the
capacity setting for the PCB will become the capacity setting of the adaptor. (Priority of capacity
setting adaptor)
YES
YES
Plug a capacitor setting
adaptor that matches the
capacity of the unit into
X23A. (See note)
Bad contact of capacity
setting adaptor or
disconnected adaptor.
Indoor unit PCB
replacement
Could be outside cause
(noise, etc.) other than
malfunction.
NO
(Q0537)
NO
Turn the power supply off once
and back on.
Is the
capacity setting
adaptor plugged into X23A
of the indoor unit
PCB?
Is AJ
displayed on the remote
controller?
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Содержание E Series
Страница 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Страница 26: ...SiAU18 715 Specifications 13 Part 2 Specifications 1 Specifications 14 1 1 Cooling Only 14 1 2 Heat Pump 23 ...
Страница 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Страница 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Страница 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Страница 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Страница 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Страница 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Страница 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Страница 449: ...SiAU18 715 vi Index ...