background image

Description

These installation instructions supplement the electric heater 

kits for installation in the following models:

DRC090, DRC102, DRC120, DRC150

DBC090, DBC102, DBC120, DBC150

DBH090, DBH102, DBH120, DBH150

These instructions should be used only as a supplement to 

unit’s installation instruction manual. If the heater kit is installed 

on a unit with DDC controls, reference the DDC user manual 

for controller configuration instructions. The controller will not 

control the heater kit unless it is properly configured.

WARNING

HIGH VOLTAGE

DISCONNECT ALL POWER BEFORE SERVICING 

OR INSTALLING THIS UNIT. MULTIPLE POWER 

SOURCES MAY BE PRESENT. FAILURE TO DO SO 

MAY CAUSE PROPERTY DAMAGE, PERSONAL 

INJURY OR DEATH.

INSTRUCTIONS

1.  Disconnect all power to the unit, both indoor and outdoor.
2.  Remove control box door.
3.  Remove blower door.
4.  Locate heater box. Remove screws holding the heater box 

cover in place (Figure 1).

HORIZONTAL SUPPLY COVER

HEATER BOX COVERS

CONTROL 

BOX DOOR

BLOWER DOOR

Figure 1

Attention Installing Personnel

As a professional installer, you have an obligation to know 

the product better than the customer. This includes all safety 

precautions and related items.

Prior to actual installation, thoroughly familiarize yourself with 

this Instruction Manual. Pay special attention to all safety 

warnings. Often during installation or repair, it is possible to 

place yourself in a position which is more hazardous than 

when the unit is in operation.

Remember, it is 

your 

responsibility to install the product safely 

and to know it well enough to be able to instruct a customer 

in its safe use.

Safety is a matter of common sense...a matter of thinking 

before acting. Most dealers have a list of specific good safety 

practices...follow them.

The precautions listed in this Installation Manual are intended 

as supplemental to existing practices. However, if there is a 

direct conflict between existing practices and the content of 

this manual, the precautions listed here take precedence.

SAFETY CONSIDERATIONS

The following symbols and labels are used throughout this 

manual to indicate immediate or potential safety hazards. It is 

the owner’s and installer’s responsibility to read and comply 

with all safety information and instructions accompanying 

these symbols. Failure to heed safety information increases 

the risk of personal injury, property damage, and/or product 

damage.

ELECTRIC HEAT KITS EHXD, EHXB, 

EHSD and EHSB for

7.5 - 12.5 TON LIGHT COMMERCIAL ROOF TOP UNITS

MODELS: DRC, DBC and DBH

INSTALLATION INSTRUCTIONS

© 2020 

19001 Kermier Rd., Waller, TX 77484

www.daikincomfort.com
P/N: IOD-7117  Date: April 2020

PROP 65 WARNING 

FOR CALIFORNIA CONSUMERS

WARNING

Cancer and Reproductive Harm -

www.P65Warnings.ca.gov

0140M00517-A

 

WARNING

Only personnel that have been trained to install, adjust, 

service  or  repair  (hereinafter,  “service”)  the  equipment 

specified  in  this  manual  should  service  the  equipment. 

The manufacturer will not be responsible for any injury 

or  property  damage  arising  from  improper  service  or 

service  procedures.  If  you  service  this  unit,  you  assume 

responsibility for any injury or property damage which may 

result. In addition, in jurisdictions that require one or more 

licenses to service the equipment specified in this manual, 

only  licensed  personnel  should  service  the  equipment. 

 

Improper installation, adjustment, servicing or repair of 

the equipment specified in this manual, or attempting to 

install, adjust, service or repair the equipment specified in 

this manual without proper training may result in product 

damage, property damage, personal injury or death

.

Содержание DRC090

Страница 1: ...rs have a list of specific good safety practices follow them The precautions listed in this Installation Manual are intended as supplemental to existing practices However if there is a direct conflict between existing practices and the content of this manual the precautions listed here take precedence SAFETY CONSIDERATIONS The following symbols and labels are used throughout this manual to indicat...

Страница 2: ...ing through the rail Figure 5 and using 5 screws supplied with this IO Figure 6 HEATING ELEMENT SCREWS FROM UNIT Figure 3 7 Connect power to kit Remove power cable from the box Connect wire leads to the line side of the power block on the heater kit s electrical panel Connect one wire lead per pole Route all leads through the blower deck and into the control box as shown in Figure 6 Connect wire l...

Страница 3: ...est unit to ensure it is functioning properly UNITS HEATER KIT MODEL NUMBER kW MINIMUM SCFM DBC090 DBH090 EH B M15 EH B M30 EH B M45 15 30 45 2400 DBC102 DBH102 EH B M15 EH B M30 EH B M45 15 30 45 2750 DBC120 DBH120 EH B M16 EH B M31 EH B M46 15 30 45 3250 DBC150 DBH150 EH B M16 EH B M31 EH B M46 15 30 45 3750 DRC102 EH D M10 EH D M15 EH D M20 EH D M30 EH D M45 10 15 20 30 45 2850 DRC120 EH D M10 ...

Страница 4: ...d forgiving to operate We use quality materials and components Finally every unit is run tested before it leaves the factory That s why we know There s No Better Quality Visit our website at www daikincomfort com for information on Products Warranties Customer Services Parts Contractor Program and Training Financing Options 2020 CUSTOMER FEEDBACK Daikin is very interested in all product comments P...