background image

7 Installation

Installation manual

8

DCC601A51

intelligent Tablet Controller

4P414342-1D – 2020.12

Connection

Cross section

Max. length

Remarks

LAN cable

100 m

▪ UTP CAT 5e or higher

▪ RJ45 connector

DIII-NET (F1/F2)

Ø0.75~1.25 mm²

(terminal sized for maximum

1.5 mm²)

Total length

(a)

: 2000 m

(<1500 m when using

shielded wire)

Max. length

(b)

: 1000 m

▪ Cable  type:  2-core  vinyl  insulated  vinyl-sheathed  cable/

vinyl cabtyre cable or 2-core shielded cable

▪ Do NOT use multicore cables with 3 or more cores

▪ Do NOT use mixed cable types

▪ NEVER bundle the cables

▪ When  using  a  shielded  cable,  connect  only  one  end  of

each shield wire to the ground

▪ Make  sure  the  wiring  is  routed  and  fixed,  so  as  NOT  to

touch unearthed accessible conductive parts

▪ Make sure a strain relief is available for each wire entering

the electrical cabinet

▪ For  more  information  on  DIII‑NET,  refer  to  the  DBACS

design guide (ED72721)

Digital Inputs
(Di1~Di4, Do)

200 m

▪ The  voltage-free  contact  connected  to  the  input  terminal

MUST be suitable for detection by 10 mA at 16 V DC

▪ For  pulse  signals:  pulse  width  20~400  ms,  pulse  interval:

100 ms or more

230 V AC power
supply to the WAGO
PSU

According to applicable

legislation (terminal sized

for maximum 4 mm²)

According to applicable

legislation

▪ Solid or stranded wire allowed

▪ The  internal  protection  of  the  WAGO  PSU  is  fused  at

2.5 A / 250 V

24 V DC power
supply to the CPU
module

According to applicable

legislation

Solid or stranded wire allowed

USB cable

5 m

Commercial USB 2.0 cable, type-A to type-B connector
(provided in the intelligent Tablet Controller kit)

(a)

Total length is the sum of all wiring in the DIII-NET network.

(b)

Max. length is the maximum distance between any 2 connection points in the DIII-NET network.

7.2.2

Connecting to other equipment

For all wiring requirements see 

"7.2.1 Wiring requirements"

 [

4

 7].

To connect DIII‑NET compatible equipment

DIII‑NET  is  a  unique  air  conditioning  equipment  communication
capability  developed  by  Daikin.  Using  DIII‑NET,  you  can  centrally
control  multiple  DIII‑NET-compatible  air  conditioning  devices  by
connecting them to your intelligent Tablet Controller.

1

Use  the  F1  and  F2  terminals  on  the  upper  part  of  the  I/O
module  to  connect  the  DIII‑NET  communication  line.  These  2
terminals have no polarity.

An  example  of  connecting  more  than  2  air  conditioning  devices  is
shown in the following figure.

Schematic wiring diagram with DIII terminals

a

b c

d

e

f

d

d

d

d

d

d

d

d

d

a

b c

DIII

F2 F1

a

Outdoor unit

b

OUT – OUT

c

IN – OUT

d

Indoor unit

e

A maximum of 7 outdoor units can be connected.

Содержание DCC601A51

Страница 1: ...Installation manual intelligent Tablet Controller English Installation manual intelligent Tablet Controller DCC601A51 ...

Страница 2: ...t audience Authorised installers Documentation set This document is part of a documentation set The complete set consists of Installation manual Installation instructions Format Paper supplied in the kit Installer reference guide Preparation of the installation reference data Format Digital files on http www daikineurope com support and manuals product information Latest revisions of the supplied ...

Страница 3: ... performed in accordance with the wiring diagram supplied with the product Make sure to install earth wiring Do NOT earth the unit to a utility pipe surge absorber or telephone earth Incomplete earth may cause electrical shock Make sure to use a dedicated power circuit NEVER use a power supply shared by another appliance Make sure to install the required fuses or circuit breakers Make sure to inst...

Страница 4: ...ller kit see 10 5 Schematic setup of the intelligent Tablet Controller 4 11 Before installing the intelligent Tablet Controller kit modules draw up an efficient plan of work using this schematic and based on the real environment it needs to be installed in 5 3 Compatible Daikin equipment The intelligent Tablet Controller solution can connect to certain Daikin units that provide a DIII NET communic...

Страница 5: ...ments Location Indoor inside an electrical cabinet The electrical cabinet must be lockable or designed to be opened only with a special tool The key or tool should be available only to service personnel must be installed in a space with no access for the general public must comply with the applicable legislation must have ingress protection class of IP4X or higher however make sure enough ventilat...

Страница 6: ...itches a RESET Button for restarting the CPU module and I O module k DIP SW Reserved for servicing Factory default all switches are set to OFF OFF n BACKUP Switch for turning on off the backup power supply for retaining the current settings provided by the internal battery Factory default OFF OFF This will be set to the ON ON position during commissioning q Lever To assist mounting dismounting the...

Страница 7: ...perating condition CPU ALIVE ALARM Normal Blink OFF Hardware failure OFF ON Power interruption OFF OFF Communication failure between CPU module and I O module for 10 seconds or more ON Blink 7 Installation 7 1 Installation of the intelligent Tablet Controller hardware The intelligent Tablet Controller components are to be mounted onto a 35 mm DIN rail inside an electrical cabinet For more informat...

Страница 8: ...on terminal sized for maximum 4 mm According to applicable legislation Solid or stranded wire allowed The internal protection of the WAGO PSU is fused at 2 5 A 250 V 24 V DC power supply to the CPU module According to applicable legislation Solid or stranded wire allowed USB cable 5 m Commercial USB 2 0 cable type A to type B connector provided in the intelligent Tablet Controller kit a Total leng...

Страница 9: ...ternally So you can use any one of them However you can only connect up to 2 wires simultaneously to each COM terminal If applicable connect the I O module s COM terminal to the negative side of the device terminals 7 2 3 Connecting the power supply to all modules For all wiring requirements see 7 2 1 Wiring requirements 47 To connect the power supply to all modules 1 Connect the power supply to t...

Страница 10: ...e data backup battery Both intelligent Tablet Controller modules are marked with the following symbol This means that electrical and electronic products may not be mixed with unsorted household waste Do NOT try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and of other parts must be done by an authorized installer and must comply with applicable...

Страница 11: ...chematic setup of the intelligent Tablet Controller USB 230 V AC RJ 45 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 OUT IN F1 F2 http cloud daikineurope com DIII NET POWER I O IF CPU IF LAN F1 F2 Di1 Di4 d e f i i i h j k 24 V DC c b g a l l L N a WAGO power supply unit b CPU module c I O module d Optional Daikin supplied tablet e Daikin Cloud Service f Daikin Cloud Service g LAN gateway optional Dai...

Страница 12: ...4P414342 1D 2020 12 Copyright 2015 Daikin 4P414342 1 D 0000000Y Verantwortung für Energie und Umwelt ...

Отзывы: