ESIE17 - 09 / 2017.11

Servicing manual

29

7 Operation

In case of a Warning or a Blocking error, the user interface 

will leave Error mode and return to the home screen when the 

cause of the error disappears.

In case of a lockout error, the boiler needs to be reset. Press 

the reset button to remove the error, but only if the cause of 

the error is gone. If the cause of the error is still there, the user 

interface will enter error mode again. When the error is solved, 

the user interface returns to the home screen.

If you  turn any of the dials or push any button of the buttons 

except  Reset  button  during  an  error,  the  user  interface  will 

display the home screen. After the timeout without any inter

-

action, instead of darkening, the user interface will enter error 

mode.

A table with all error codes, the reasons for their 

appearance, and possible solutions, is located at 

the very end of this manual.

NOTICE

7.10 Menu Functions

Push the Menu button while you are at homescreen to go the 

Menu screen. This is menu level 1 screen. To switch between 

Info, User Settings and Service Settings, turn the left dial. To 

leave the menu and return to the home screen, press “Back” 

for 2 seconds. When there is no user interaction for one min-

ute, the user interface will leave the menu and switch to the 

blank screen.

a) Not applicable if the sensor is not connected.

b) Maximum value during central heating operation:

Maximum value during domestic hot water operation = 100%

c) A10=0: Standby mode, burner is not active

A10=1: Start-up, preparation to ignition

A10=2: Ignition and flame stabilisition phase

A10=3: Release control (burner is on, operation phase)

A10=4: Post-purge phase

To  go  into  the  Info  menu,  press  the  Enter  Button  when  the      

icon is displayed on the menu level 1 screen. 

Select an index between 00 and 14 with the right dial.

Press the Back button to return to menu level 1 screen.

a

a Change index with right dial

INFO MENU

Parame-

ter No

Description (Short)

Unit

A00

Actual flow temperature

ºC

A01

Actual return temperature

ºC

A02

Actual DHW temperature

ºC

A03

Actual flue temperature

ºC

A04

(a)

Actual outdoor temperature (if outdoor 

sensor is connected, otherwise “--”)

ºC

A05 

(a)

Actual solar temperature (if solar sen

-

sor is connected, otherwise “--”)

ºC

A06

Actual water pressure

bar

A07

Actual domestic hot water flow rate

l/min

A08

(b)

Current set point of burner capacity

%

A09

(b)

Actual capacity of boiler in relation to 

nominal capacity

%

A10

(c) 

Actual phase of the burner

none

A11

Status of ON-OFF room thermostat, 

indicate heat demand (HC1)

none

A12

Actual error code of boiler

none

A13

Actual fan speed (rpm/100)

rpm

A14

Current setpoint of boiler pump

%

Error 

type

Boiler opera

-

tion

User interface and Daikin Eye

War-

ning

Continue

The Daikin Eye does not enter 

Error mode if burner is on. It turns 

to red when the burner is off. The 

LCD screen stays active and 

displays the error code.

Bloc-

king

Blocked, turns 

back to opera

-

tion if 

cause disap

-

pears.

The Daikin Eye enters Error 

mode. The LCD screen stays acti

-

ve and displays the error code.

Lockout

Blocked and a 

reset 

is required.

The Daikin Eye enters error 

mode. The LCD screen stays ac

-

tive and displays the error code. 

Also, the      icon starts blinking, 

indicating that a reset is required.

Model

Maximum CH capacity

D2CND028

84

D2TND028

84

D2CND035

100

D2TND035

100

7.10.1  Info Menu

The  Info  menu  covers  all  possible  information  that  is  made 

available to the end-user and to the installer. This parameters 

are read only and can not be changed.

Содержание D2CND028A1AA

Страница 1: ...Servicing manual Wall mounted condensing boiler D2CND028A1AA D2CND028A4AA D2CND035A1AA D2CND035A4AA D2TND028A4AA D2TND035A4AA English Servicing manual Wall mounted condensing boiler...

Страница 2: ...A1AA D2CND028A4AA D2CND035A1AA D2CND035A4AA D2TND028A4AA D2TND035A4AA Wall mounted condensing boiler ESIE17 09 2017 11 Servicing manual 2 LOG Version Code Description Date ESIE17 09 Document release 1...

Страница 3: ...Gas air ratio No need to adjust 24 6 4 To commission the unit 24 6 4 1 To commission the central heating 24 6 4 2 To commission the central heating capacity setting 24 6 4 3 To commission the domesti...

Страница 4: ...which is composed of an LCD screen push buttons and two dials and which is located on the front cover of the appliance The appliance is equipped with several safety systems to pro tect it against dang...

Страница 5: ...ty system This function protects the appliance and heating installation from frost damages Itiscontrolledbytheflowtemperaturesensorwhichis located at the outlet of the main heat exchanger This protect...

Страница 6: ...ode 15 Ionization electrode 16 High limit thermostat 17 Fan 18 Return temperature sensor 19 Silencer 20 Automatic air vent pump 21 Water pressure sensor 22 By pass 23 Boiler pump 24 Domestic hot water...

Страница 7: ...mperature min max G20 C 57 5 76 4 57 5 81 7 57 5 76 4 57 5 81 7 Combustion products temperature min max G31 C 57 5 74 5 57 2 80 2 57 5 74 5 57 2 80 2 CO2 Emission at nominal and minimum heat input G20...

Страница 8: ...14_FLOW X4 15_OWC X4 16_OWC X3 1_PwmWh X3 2_PwmB1 X3 3_ReWhSw X3 4_Gnd X3 5_5v X2 8_LP1 X2 1_SOLs X2 2_SOL X2 3_RTs X2 4_RT X2 5_NPSRT X2 6_LPSRT X2 7_NP1 X5 X4 X3 X2 X1 X1 1_NP X1 2_LP X1 3_NI X1 4_...

Страница 9: ...Number 30 32 24 26 14 18 3 3 Spare parts To ensure long lasting operation of the appliance always use original spare parts Spare parts must be ordered from spare parts catalog by specifying the relat...

Страница 10: ...omestic Hot Water Circuit Isolate the appliance from power supply and closedown the gas valve Close all the isolating valves on the central heating circuit Open the drain valve 1 and drain the central...

Страница 11: ...iance Isolate the appliance from power supply and closedown the gas valve Undo M5 screw at the figure 1 Remove the assembly clips of front cover 2 Remove the front cover by pulling up 3 Undo 2 sheet s...

Страница 12: ...p wire connectors by pushing pawls help of flat screwdriver 2 Disconnect the wire connector of flow sensor it is used only C model 3 and water pressure sensor 4 Disconnect the wire connector of 3 way...

Страница 13: ...t s housing and disconnect the sensor 13 It is used only C model Take out cable connections of fan manually 14 Re assemble in reverse order Be careful all electrical cables during the removal of cable...

Страница 14: ...ove the gas supply pipe from the gas valve and brass nipple by using wrench 1 Unscrew the 2xM5 screws that connect gas manifold and burner hood 2 Seperate the gas manifold from the burner hood clip an...

Страница 15: ...sensors and high limit thermostat refer to Section 4 3 Take out the syphon parts by turning manually 1 Unscrew the screws that connect hermetic cabinet and right cover 2 Remove the flow and return pi...

Страница 16: ...o the screws of the electrodes from the heat exchang er and take out the electrodes 11 Take out the air vent which locates on the main heat ex changer by using wrench 12 Undo 2xM6 screw that connects...

Страница 17: ...motor from return hydroblock group by sliding it to the left 1 Disconnect 3 way valve motor s stepper motor wire connector with the help of flat screwdriver 2 Undo the 3 screws that connects to herme...

Страница 18: ...DHW flow CH flow installation pipes from the boiler by using wrench refer to Section 4 1 Open the appliance refer to Section 4 2 Take out the expansion vessel refer to Section 4 10 Remove the fasteni...

Страница 19: ...Isolate the appliance from power supply and closedown the gas valve Drain the water from the boiler refer to Section 4 1 Open the appliance refer to Section 4 2 Remove the left cover of the boiler uns...

Страница 20: ...pawls refer to Section 4 5 Undo the screw between flow hydroblock and plate heat exchanger 1 Undo the screw that between return group and plate heat exchanger 1 Remove the plate heat exchanger from th...

Страница 21: ...Section 4 10 Unscrew the 3 screws that connect PCB and control panel 5 Remove the buttons from back of the control panel 6 Remove Daikin eye s 2 screws 7 Disconnect Daikin eye s wire connector 8 Isola...

Страница 22: ...n the pump and heat exchanger are opened Vent the air from the installation with the manual air vent screws on the radiators Make sure screws are tightened after venting If after the purge the pressur...

Страница 23: ...optionals Below you can see the Cable glands placement Note Boiler Sensor is used only T model Note Illustration of plugging of connector to X1M terminal Holes on the bottom sheet that are reserved fo...

Страница 24: ...eat demand 5 tst 100 caption will appear on the screen This means boiler is operating at nominal capacity Check nominal ca pacity operation 6 To quit sweeper mode again press Cancel and Menu buttons t...

Страница 25: ...ng or domestic hot water the ring flashes to its maximum then constantly keeps glowing during burner operation with blue LED 7 1 7 Error The Daikin eye will go into error mode when a warning lockout o...

Страница 26: ...ature System Pressure at stand by mode 7 3 2 Selecting Operation Mode The operation mode can be changed by pushing the Mode button 7 4 Description of the Operation Modes 7 4 1 Stand by Mode In stand b...

Страница 27: ...iler No room ther mostat or outdoor sensor are connected The central heating water temperature setpoint is displayed The setpoint can be adjusted with the left dial The icon is shown on the screen whe...

Страница 28: ...hours Note Independent of personal use pattern Comfort mode preheating function could be adjusted to operate continuously from the user settings For example When the domestic hot water DHW mode is ac...

Страница 29: ...e A10 3 Release control burner is on operation phase A10 4 Post purge phase To go into the Info menu press the Enter Button when the icon is displayed on the menu level 1 screen Select an index betwee...

Страница 30: ...l room tem perature setpoint when there is a heat demand U06 When On Off Room thermostat and outdoor sensor are both connected this parameter value is the virtual room tem perature setpoint when there...

Страница 31: ...Opentherm thermostat is switched off no heat demand boiler is either switched off 0 or operates in redu ction mode 1 P01 Weather compensation building condition parameter It is used in flow setpoint c...

Страница 32: ...de Visible only for storage tank type models P15 Max temperature that can be adjusted by left dial when setting central heating flow temperature P16 This parameter is a read only parameter which shows...

Страница 33: ...5 kW Tflow return 10 C 10 circuits and lenght of the each circuit is 80 metres without an additional pump When the boiler is connected to an UFH system the following parameter changes must certainly b...

Страница 34: ...ces starting gas air ratio will be far from average value which may also result in ignition problems delayed or loud ignition If such problems are present C02 parameter must be optimized first If C02...

Страница 35: ...asing may cause loud ignition C03 This parameter is used to increase maximum allowable flue duct length by increasing fan speed Adjust this parameter to 3 to use longer flue ducts for C13x and C33x ty...

Страница 36: ...adjustment set the pass word as 043 c For 100 calibration and C12 C13 adjustment set the password as 046 Press Enter button The boiler will start calibration accord ing to above mentioned input value...

Страница 37: ...tant and set to 45 C 2 Pump runs at 100 capacity Function is active for 10 minutes of burner operation After function is ended boiler operates according to central heating setpoint adjusted by the cus...

Страница 38: ...CB can be changed at field without need to change the PCB itself The BCC con tains all control parameters and safety parameters 9 1 1 Spare Part PCB PBC s that will be used as spare part all have 24 k...

Страница 39: ...69 error code will still be shown on display Resetting the boiler will remove the error 9 1 4 Error during Parameter transfer If an error occurs during the Parameter transfer or if parameter update is...

Страница 40: ...described in this manual 12 66 Ion base val ue exceeds lower factory limit Reset the boiler Make a manuel calibration Check the ionization elecktrode it s cable connection and it s earth cable Replac...

Страница 41: ...s not as desired ERROR CODE REASON ELIMINATION 81 01 Flow tem perature sensor fault Check continuity between the sen sor and PCB replace wire harness if necessary Check flue tempera ture sensor resist...

Страница 42: ...it of the building should be checked and voltage stabiliser should be used for smooth operation U4 65 Opentherm RT connection is defective Boiler operates as if Opentherm room thermostat not connected...