Wall-mounted condensing boiler
ESIE17 - 09 / 2017.11
Servicing manual
22
5.1 Filling the System With Water
5.2 Converting For Use With a Different Type of
Gas
After all system connections are performed with care, perform
the following steps:
•
Connect the appliance to the main power supply. Due to
low pressure, error code “Err HJ-09” will appear on the
user interface and The Daikin Eye light will be red.
•
Open all radiator valves.
•
Set all isolating valves to vertical (open ) position.
•
Measure system water height
•
Slowly turn the filling valve until pressure reaches a value
around 0.8 bar for system heights up to 6 metres. For
longer system heights, refer to below table to determine
filling pressure. Filling operation should be done slowly.
When pressure exceeds 0.8 bar, the error code will dis
-
appear and Daikin Eye light will turn to blue. Turn off the
filling valve.
•
System pressure value can be monitored from the user
interface.
•
Make sure the automatic air vent valves located on the
pump and heat exchanger are opened. Vent the air from
the installation with the manual air vent screws on the
radiators. Make sure screws are tightened after venting.
•
If after the purge the pressure decreases below 0.8 bar,
refill the system with water until the pressure reaches 0.8
bar again.
•
Check the central heating circuit - especially the cou
-
plings of the circuit - for leakage.
•
Isolate the boiler from power mains.
To convert the system to be used with a different type of gas:
Open the front cover of the appliance as described in this
manual.
To set natural gas, adjust screw on the gas valve to “1” posi
-
tion (1)
To set LPG, adjust the screw to “2” position .
Mount the front cover, connect the appliance to the main pow
-
er supply.
Filling the system with filling valve
System Water Height
h (metres)
Charge Pressure
Gas conversion operation can only be carried out by
qualified competent persons.
WARNING
Isolate the boiler from the power mains before gas
conversion operation.
DANGER
5 Installation information
h
B
(1)
h
System
charge
pressure
Up to
6 m
0.8 bar
7 m
0.9 bar
8 m
1.0 bar
9 m
1.1 bar
10 m
1.2 bar
11 m
1.3 bar
12 m
1.4 bar
13 m
1.5 bar
Gas conversion can be changed with C00 ( refer
to Scot Parameters).
INFORMATION
5 INSTALLATION INFORMATIONS