Servicing manual

31

7.10.2  User settings menu  

User  settings  menu  comprises  parameters  that  can  be 

changed and adjusted by users.

7.10.2.1  Detailed Explanations of User Parameters

U00: 

 When using outdoor sensor, above this parameter value 

of outside temperature, boiler senses the season as summer 

and not activate central heating although there is demand.

U01:

 This value is used when only outside sensor is connect-

ed to the boiler (No Opentherm RT connection). The param

-

eter heating slope is important to adapt the weather compen

-

sation to the individual heating system, the building and the 

thermal insulation. The heating slope can be adjusted from 0 

to 40. The higher the value heating slope, the higher the boiler 

central heating set temperature.

Note: 

To activate Weather compensation, heating slope value 

must be higher than “5”.

U02:

 Enabling / disabling Central Heating ECO mode.  

1 = enabled, 0 = disabled

U03:

 Enabling / disabling DHW Comfort mode.  

1 = enabled, 0 = disabled

U04:

 Domestic hot water setvalue (Same function that can be 

done via right dial when DHW mode is enabled).

U05:

 When On-Off Room thermostat and outdoor sensor are 

both  connected, this parameter value is the virtual room tem

-

perature setpoint when there is a heat demand. 

U06:

 When On-Off Room thermostat and outdoor sensor are 

both connected, this parameter value is the virtual room tem

-

perature setpoint when there is no heat demand.

Note: 

For this parameter value to be active, reducing mode 

have to be enabled by your service agent, otherwise central 

heating mode will not be activated when there is no heat de-

mand. 

U07: 

When On-Off Room thermostat is connected and out

-

door sensor is not connected, this parameter value is the cen

-

tral heating water temperature setpoint when there is a heat 

demand.

U08: 

When On-Off Room thermostat is connected and out

-

door  sensor  is  not  connected,  this  parameter  value  is  the 

central heating water tempearture setpoint when there is no 

a heat demand.

Note:

 For this parameter value to be active, Reducing mode 

have to be enabled by your service agent, otherwise central 

heating mode will not be activated when there is no het de-

mand.

U09: 

If parameter is 1, comfort mode preheating will depend

on the user record. It will preheat the water according to

the previous day user records.

If parameter is 2, comfort mode preheating will be

independent of the user record, and at the highest

comfort level (3-star comfort according to EN 13302).

If parameter is 24, comfort mode preheating will be

independent of the user record.

U10: 

Room temperature setpoint  used by Daikin Opentherm 

RT  during  “Night  mode”.  Only  visible  in  case  Daikin  Open

-

therm room thermostat is connected.

To  go  into  the  User  Settings  menu,  press  the  Enter  Button 

when the         icon is displayed on the menu level 1 screen.

You can see the parameter values on menu level 2. 

Select an index between “00” and “10” with the right dial. 

Press “Enter” when the parameter that you want to change is 

displayed. This  screen is menu level 3 screen.

Up  and  Down  arrows  will  appear,  and  you  will  be  able  to 

change the parameter with the right dial. 

Press “Enter” to confirm or “cancel” to cancel. You will return 

to  menu level 2 after pressing “Enter” or “Back”.

Note:

 

Virtual room temperature means, setpoint which adjust 

at the boiler’s screen when ODS connects the boiler.   

7 Operation

USER SETTINGS

Parame-

ter No

Description 

Unit

Factory 

setting

Range

U00

Summer-Winter 

switch over tempe

-

rature

ºC

20

10 - 30

U01

Heating slope 

none

0

0 - 40

U02

Central heating 

ECO mode

none

0

0 - 1

U03

Domestic hot water 

comfort mode

none

0

0 - 1

U04

DHW set value

ºC

50

35 - 60

U05

Set value for the 

room thermostat at 

day mode

ºC

21

10 - 30

U06

Set value for the 

room thermostat at 

reduced mode

ºC

18

10 - 30

U07

Set value for the 

flow temperature at 

day mode

ºC

50

30 - 80

U08

Set value for the 

flow temperature at 

reduced mode

ºC

35

30 - 80

U09

Domestic hot water 

comfort mode user 

record dependancy

none

1

1,2 or 

24

U10

Room Temp. setpo

-

int used by Daikin 

Opentherm RT 

during night.

ºC

18

10 - 30

Содержание D2CND024A1AA

Страница 1: ...Servicing manual Wall mounted condensing boiler D2CND024A1AA D2CND024A4AA D2TND012A4AA D2TND018A4AA D2TND024A4AA English Servicing manual Wall mounted condensing boiler...

Страница 2: ...CND024A1AA D2CND024A4AA D2TND012A4AA D2TND018A4AA D2TND024A4AA Wall mounted condensing boiler ESIE17 09 2017 11 Servicing manual 2 LOG Version Code Description Date ESIE17 09 Document release 1 11 201...

Страница 3: ...s 26 7 1 2 LCD screen 26 7 1 3 Status icons 26 7 1 4 Daikin Eye 26 7 1 5 Stand by 26 7 1 6 Flame 26 7 1 7 Error 26 7 2 Operating The Appliance 27 7 2 1 Low Water Temperature Function 27 7 2 2 Electron...

Страница 4: ...s composed of an LCD screen push buttons and two dials and which is located on the front cover of the appliance The appliance is equipped with several safety systems to pro tect it against dangerous c...

Страница 5: ...w temperature sensor which is located at the outlet of the main heat exchanger This protection ac tivates the boiler pump when the water temperature drops below depends on P03 parameter value and it a...

Страница 6: ...ostat 17 Fan 18 Return temperature sensor 19 Silencer 20 Automatic air vent pump 21 Water pressure sensor 22 By pass 23 Boiler pump 24 Domestic hot water flow sensor 25 Domestic hot water flow limiter...

Страница 7: ...56 68 56 77 Combustion products temperature min max G31 C 56 60 56 68 55 76 Maximum combustion products temp at nominal heat input C 80 82 90 CO2 Emission at nominal and minimum heat input G20 9 0 0...

Страница 8: ...14_FLOW X4 15_OWC X4 16_OWC X3 1_PwmWh X3 2_PwmB1 X3 3_ReWhSw X3 4_Gnd X3 5_5v X2 8_LP1 X2 1_SOLs X2 2_SOL X2 3_RTs X2 4_RT X2 5_NPSRT X2 6_LPSRT X2 7_NP1 X5 X4 X3 X2 X1 X1 1_NP X1 2_LP X1 3_NI X1 4_...

Страница 9: ...stable spanner Number 30 32 24 26 14 18 3 3 Spare parts To ensure long lasting operation of the appliance always use original spare parts Spare parts must be ordered from spare parts catalog by specif...

Страница 10: ...Domestic Hot Water Circuit Isolate the appliance from power supply and closedown the gas valve Close all the isolating valves on the central heating circuit Open the drain valve 1 and drain the centr...

Страница 11: ...from power supply and closedown the gas valve Undo M5 screw at the figure 1 Remove the assembly clips of front cover 2 Remove the front cover by pulling up 3 Undo 2 sheet screw holding control panel 4...

Страница 12: ...connector of flow sensor 2 and pressure sensor 3 Disconnect the wire connector of 3 way valve refer to 4 6 1 Dismantle the ignition electrode and earth cable from the power supply 4 Firstly loosen th...

Страница 13: ...socket s housing and disconnect the sensor 13 Take out cable connections of fan manually 14 Re assemble in reverse order Be careful all electrical cables during the removal of cable group wire harnes...

Страница 14: ...e gas supply pipe from the gas valve and brass nipple by using wrench 1 Unscrew the 2xM5 screws that connect gas manifold and burner hood 2 Seperate the gas manifold from the burner hood clip and take...

Страница 15: ...low return and flue NTC sensors and high limit thermostat refer to Section 4 3 Take out the syphon parts refer to Section 4 8 Unscrew the screws that connect hermetic cabinet and right cover 1 Remove...

Страница 16: ...nted condensing boiler ESIE17 09 2017 11 Servicing manual 16 4 Part replacement Remove the screw holding the hermetic cabinet with main heat exchanger M5 allen 9 Detach the main heat exchanger by push...

Страница 17: ...nti nel s products which are appropriate for cleaning of heat exchanger inside Inspect the heat exchanger from the top and bottom Take any foreign object Use the cleaning tool into the heat exchanger...

Страница 18: ...2 Undo the screws that connect to hermetic cabinet to the pump 3 Undo the 2 screws that connect to hermetic cabinet to the pump 4 for T models Loosen the union joint that provides the return pipe pump...

Страница 19: ...the DHW flow CH flow installation pipes from the boiler by using wrench refer to Section 4 1 Open the appliance refer to Section 4 2 Take out the expansion vessel refer to Section 4 10 Remove the fast...

Страница 20: ...osedown the gas valve Drain the water from the boiler refer to Section 4 1 Open the appliance refer to Section 4 2 Take out the silencer refer to Section 4 4 Remove the syphon part from condensate sum...

Страница 21: ...efer to Section 4 2 Remove the left cover of the boiler unscrew the screws that connects hermetic cabin and left cover 1 Undo the screws which connect expansion vessel and flow hydroblock 2 Disconnect...

Страница 22: ...support s 3 screws holding the main pcb and remove the cable support 4 Unscrew the 3 screws that connect PCB and control panel 5 Isolate the appliance from power supply and closedown the gas valve Ope...

Страница 23: ...pump and heat exchanger are opened Vent the air from the installation with the manual air vent screws on the radiators Make sure screws are tightened after venting If after the purge the pressure dec...

Страница 24: ...w you can see the Cable glands placement Holes on the bottom sheet that are reserved for cable glands are covered with insulation material The insulation material must be bored if glands are to be use...

Страница 25: ...fter first power ON the boiler does not increase its capacity above a preset value for about 12 minutes even if there is demand First 0 2 minutes The electronic gas adapti ve system calibrates itself...

Страница 26: ...ashes to its maximum then constantly keeps glowing during burner operation with blue LED 7 1 7 Error The Daikin eye will go into error mode when a warning lockout or blocking error occurs During the e...

Страница 27: ...re at stand by mode 7 3 2 Selecting Operation Mode The operation mode can be changed by pushing the Mode button 7 4 Description of the Operation Modes 7 4 1 Stand by Mode In stand by mode both central...

Страница 28: ...o room ther mostat or outdoor sensor are connected The central heating water temperature setpoint is displayed The setpoint can be adjusted with the left dial The icon is shown on the screen when cent...

Страница 29: ...Note Independent of personal use pattern Comfort mode preheating function could be adjusted to operate continuously from the user settings For example When the domestic hot water DHW mode is activate...

Страница 30: ...ximum value during domestic hot water operation 100 c A10 0 Standby mode burner is not active A10 1 Start up preparation to ignition A10 2 Ignition and flame stabilisition phase A10 3 Release control...

Страница 31: ...onnected this parameter value is the central heating water tempearture setpoint when there is no a heat demand Note For this parameter value to be active Reducing mode have to be enabled by your servi...

Страница 32: ...0 20 P19 Min CH flow temp setpoint C 30 10 30 P00 In case Opentherm thermostat is switched off no heat demand boiler is either switched off 0 or operates in redu ction mode 1 P01 Weather compensation...

Страница 33: ...ble only for storage tank type models P15 Max temperature that can be adjusted by left dial when setting central heating flow temperature P16 This parameter is a read only parameter which shows the co...

Страница 34: ...0 C 10 circuits and lenght of the each circuit is 80 metres without an additional pump When the boiler is connected to an UFH system the following parameter changes must certainly be done Parameter Ma...

Страница 35: ...ir ratio will be far from average value which may also result in ignition problems delayed or loud ignition If such problems are present C02 parameter must be optimized first If C02 parameter change i...

Страница 36: ...may cause loud ignition C03 This parameter is used to increase maximum allowable flue duct length by increasing fan speed Adjust this parameter to 3 to use longer flue ducts for C13x and C33x types of...

Страница 37: ...e pass word as 043 c For 100 calibration and C12 C13 adjustment set the password as 046 Press Enter button The boiler will start calibration ac cording to above mentioned input values LED s on the scr...

Страница 38: ...set to 45 C 2 Pump runs at 100 capacity Function is active for 10 minutes of burner operation After function is ended boiler operates according to central heating setpoint adjusted by the customer an...

Страница 39: ...mall plug which contains a programmed memory With BCC set of parameters inside the PCB can be changed at field without need to change the PCB itself The BCC con tains all control parameters and safety...

Страница 40: ...or code will still be shown on display Resetting the boiler will remove the error 9 1 4 Error during Parameter transfer If an error occurs during the Parameter transfer or if parameter update is not i...

Страница 41: ...12 66 Ion base val ue exceeds lower factory limit Reset the boiler Make a manuel calibration Check the ionization elecktrode it s cable connection and it s earth cable Replace if defective ER ROR CODE...

Страница 42: ...leshooting ERROR CODE REASON ELIMINATION 81 01 Flow tem perature sensor fault Check continuity between the sen sor and PCB replace wire harness if necessary Check flue tempera ture sensor resistance u...

Страница 43: ...the building should be checked and voltage stabiliser should be used for smooth operation U4 65 Opentherm RT connection is defective Boiler operates as if Opentherm room thermostat not connected Check...

Страница 44: ...TMA S STEMLER SAN T C A K kbakkalk y Mah Kay da Cad No 1 Kat 21 22 34750 Ata ehir STANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr ESIE17 09 2017 11 C...

Отзывы: