Advanced Setup Table
35
FD = Factory Default Setting
Step# Description
Pg# Range
FD
1
Set Clock
18 12A - 12A
2
Set Day of the Week
18 Monday - Sunday
3
Backlight
19 On, Off, 6pm-6am
Off
4
Night Dimmer
19 On/Off
Off
5
Night Dimmer Start Time
19 12A - 12A
8:00PM
6
Night Dimmer Stop Time
19 12A - 12A
6:00AM
7
Fan On or Fan Auto
19 Fan, Fan Auto
Fan Auto
8
Setpoint Limits
20 On, Off
Off
9
Maximum Heat Setpoint Limit
20 35 - 99 Degrees
74
10
Minimum Cool Setpoint Limit
20 35 - 99 Degrees
70
11
Current Service Filter Runtime Hours
21 0 - 1999 Hours
0
12
Current Service Filter Calendar Days
21 0 - 720 Days
0
13
Set Service Filter Runtime Hours
21 0-1999 Hours
0
14
Set Service Filter Calendar Days
21 0 - 720 Days
0
15
Cycles Per Hour
22 No Limit, 2, 3, 4, 5, 6
6
16
Compressor Minimum Off Minutes
22 0, 3, 5 Minutes
5
17
Min. Heat/Cool Setpoint Difference
22 0 - 6
2
18
1st Stage Deadband
23 1 - 6 Degrees
2
19
Second Stage Deadband
23 0 - 10 Degrees
2
20
Minutes Between 1st and 2nd Stage
23 0 - 60 Minutes
2
21
2nd Stage Turnoff Point
23 Deadband, Setpoint
Deadband
22
Fan Off Delay
24 0, 120 Seconds
0
23
Maximum Override Time
24 1, 2, 3 or 4 hours
4
24
F / C
24
Fahrenheit (F), or Celsius C
F
25
Comfort Recovery
25 On, Off
Off
26
Pre-Occupancy Fan Purge
25
0 - 3 Hours in 15 minute
increments, 0 + Off
0
27
Dry Contact Polarity
26 Open, Closed
Open
28
Dry Contact Use
26
Condensate Pan, Holiday,
Holiday
FDD, Occupied
29
Skyport
27 On, Off
On
30
Local API
27 On, Off
Off
31
Available Modes
27
Heat, Cool, Heat or Cool, Auto
Auto
32
Show Clock
27 On, Off
On
TO ENTER MENUS ..... BUTTON PRESS
Setup Steps ................. MODE & OVERRIDE for 5 sec.
Time Schedule ............ MODE & UP for 2 seconds
Emergency Heat ......... UP & OVERRIDE for 2 seconds
TO ENTER MENUS .....BUTTON PRESS
Lockout Buttons ..........MODE, UP & DOWN for 2 sec.
Calibration ....................MODE & DOWN for 2 sec., then MODE
Wireless Setup ...........OVERRIDE for 5 Seconds
Содержание D2270C
Страница 43: ...Printed on recycled paper P N 88 1278 07 18 ...