Comfort Recovery (Setup step 25)
With Comfort Recovery on, the thermostat will
attempt to reach the OCCUPIED 1 setpoint
temperature at the exact time programmed into
the thermostat. Comfort Recovery, only works
when the thermostat enters the OCCUPIED 1 from the UNOCCUPIED.
For example, if OCCUPIED 1 is set for 6am at 72°F heating and 75°F
cooling, the thermostat will turn the system on before 6am in an effort
to bring the temperature to its correct setting at exactly 6am. The
thermostat learns from experience, how early to turn on, so please
allow 4-8 days after a program change or after initial installation to give
Comfort Recovery time to adjust. If used with a heat pump, electric strip
heat will be disabled while Comfort Recovery is active.
Pre-Occupancy Fan Purge (Setup step 26)
When this feature is activated, the fan will turn
on during an unoccupied period at a preset
amount of time prior to Occupied 1. This
preoccupancy fan purge timer may be set from
zero to three hours, in 15 minute increments.
Zero (0) means this feature is turned off.