11
|
Commissioning
Installer reference guide
49
CTXM-A, FTXM-A, ATXM-A
Daikin room air conditioner
4P518023-17P – 2023.06
There are NO
loose connections
or damaged electrical components in the switch box.
The
insulation resistance
of the compressor is OK.
There are NO
damaged components
or
squeezed pipes
on the inside of the indoor and
outdoor units.
There are NO
refrigerant leaks
.
The correct pipe size is installed and the
pipes
are properly insulated.
The
stop valves
(gas and liquid) on the outdoor unit are fully open.
11.3 To perform a test run
Prerequisite:
The power supply MUST be in the specified range.
Prerequisite:
Test run may be performed in cooling or heating mode.
Prerequisite:
Refer to the operation manual of the indoor unit for setting
temperature, operation mode….
1
In cooling mode, select the lowest programmable temperature. In heating
mode, select the highest programmable temperature. The test run can be
disabled if necessary.
2
When the test run is finished, set the temperature to a normal level. In cooling
mode: 26~28°C, in heating mode: 20~24°C.
3
Make sure that all functions and parts are working properly.
4
The system stops operating 3 minutes after the unit is turned OFF.
11.3.1 To perform a test run using the wireless remote control
1
Press
to switch the system on.
2
Press and
simultaneously.
3
Press
, select and press
.
Result:
Test run operation will stop automatically after about 30 minutes.
4
To stop operation sooner, press
.