Troubleshooting by Error Code
SiUS341802E
259
Service Diagnosis
2.60 Transmission Error between Indoor Units and Outdoor
Units
Error Code
U4
Applicable
Models
All indoor unit models
All outdoor unit models
Method of Error
Detection
Microcomputer checks if transmission between indoor and outdoor units is normal.
Error Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Short circuit in indoor-outdoor or outdoor-outdoor transmission wiring (F1/F2), or wrong wiring
Outdoor unit power supply is OFF
System address does not match
Defective indoor unit PCB
Defective outdoor unit PCB