SiUS341802E
Field Settings from Remote Controller
Field Settings and Test Operation
112
1.6
List of Field Settings for Outdoor-Air Processing Unit
: Factory setting
+
: The same value continues.
1.7
Setting of Operation Control Mode
The operation control mode is compatible with a variety of controls and operations by limiting the functions of the
operation remote controller. Furthermore, operations such as remote controller ON/OFF can be limited in
accordance with the combination conditions. (Refer to information in the next page.)
Central remote controller is normally available for operations. (Except when centralized monitor is connected)
Contents of Control Modes
20 modes consisting of combinations of the following 5 operation modes with temperature and operation mode
setting by remote controller can be set and displayed by operation modes 0 through 19.
ON/OFF control impossible by remote controller
Used when you want to turn ON/OFF by central remote controller only.
(Cannot be turned ON/OFF by remote controller.)
OFF control only possible by remote controller
Used when you want to turn ON by central remote controller only, and OFF by remote controller only.
Centralized
Used when you want to turn ON by central remote controller only, and turn ON/OFF freely by remote
controller during set time.
Individual
Used when you want to turn ON/OFF by both central remote controller and remote controller.
Timer operation possible by remote controller
Used when you want to turn ON/OFF by remote controller during set time and you do not want to start
operation by central remote controller when time of system start is programmed.
Mode
No.
First
Code
No.
Setting Contents
Second Code No.
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
10
(20)
0
Filter contamination
2500 hr
1250 hr
—
—
—
—
—
—
—
—
—
—
—
—
—
3
Display time to
clean air filter
calculation
Display
No
display
—
—
—
—
—
—
—
—
—
—
—
—
—
12
(22)
1
External ON/OFF
input
Forced
OFF
ON/OFF
control
—
—
—
—
—
—
—
—
—
—
—
—
—
5
Power failure
automatic reset
Not
equipped
Equipped
—
—
—
—
—
—
—
—
—
—
—
—
—
14
(24)
3
Discharge
pipe
temperature
(cooling)
°C
13
14
15
16
17
18
19
20
21
22
23
24
25
+
25
+
25
+
°F
55.4
57.2
59
60.8 62.6 64.4
66.2
68
69.8 71.6 73.4 75.2
77
+
77
+
77
+
4
Discharge
pipe
temperature
(heating)
°C
18
19
20
21
22
23
24
25
26
27
28
29
30
+
30
+
30
+
°F
64.4
66.2
68
69.8 71.6 73.4
75.2
77
78.8 80.6 82.4 84.2
86
+
86
+
86
+
Содержание Aurora Series
Страница 316: ...Wiring Diagrams SiUS341802E 303 Appendix 1 Wiring Diagrams 1 1 Outdoor Unit RXLQ72TATJU 2D112580A ...
Страница 317: ...SiUS341802E Wiring Diagrams Appendix 304 RXLQ96 120TATJU 2D112581A ...
Страница 318: ...Wiring Diagrams SiUS341802E 305 Appendix RXLQ72TAYDU 2D112582A ...
Страница 319: ...SiUS341802E Wiring Diagrams Appendix 306 RXLQ96 120TAYDU 2D112583A ...
Страница 320: ...Wiring Diagrams SiUS341802E 307 Appendix RXLQ72 96 120TAYCU RXYQ72 96 120 144 168TAYCU 2D112579A ...
Страница 330: ...Wiring Diagrams SiUS341802E 317 Appendix 1 3 2 Energy Recovery Ventilator VAM Series VAM300 470 600GVJU 3D073269C ...
Страница 331: ...SiUS341802E Wiring Diagrams Appendix 318 VAM1200GVJU 3D073270C ...
Страница 332: ...Revision History Month Year Version Revised contents 04 2018 SiUS341802E First edition ...