manualshive.com logo in svg
background image

Installer reference guide 

Daikin room air conditioner

FTXF20D5V1B
FTXF25D5V1B
FTXF35D5V1B
FTXF42D5V1B

ATXF20D5V1B
ATXF25D5V1B
ATXF35D5V1B
ATXF42D5V1B

Questo manuale d’istruzione è fornito da trovaprezzi.it. Scopri tutte le offerte per 

Daikin ATXF35D/

ARXF35D

 o cerca il tuo prodotto tra le 

migliori offerte di Condizionatori e Deumidificatori

Содержание ATXF35D

Страница 1: ...F25D5V1B FTXF35D5V1B FTXF42D5V1B ATXF20D5V1B ATXF25D5V1B ATXF35D5V1B ATXF42D5V1B Questo manuale d istruzione fornito da trovaprezzi it Scopri tutte le offerte per Daikin ATXF35D ARXF35D o cerca il tuo...

Страница 2: ...6 To open the service cover 27 6 3 Installing the indoor unit 28 6 3 1 Precautions when installing the indoor unit 28 6 3 2 To install the mounting plate 28 6 3 3 To drill a wall hole 28 6 3 4 To remo...

Страница 3: ...10 1 To set a different address 44 11 Commissioning 46 11 1 Overview Commissioning 46 11 2 Checklist before commissioning 46 11 3 To perform a test run 47 11 3 1 To perform a test run in winter season...

Страница 4: ...60335 2 40 is the applicable standard Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you MUST read befo...

Страница 5: ...out the box How to unpack the units and remove their accessories About the unit System layout Operation range Preparation What to do and know before going on site Installation What to do and know to i...

Страница 6: ...1 Meaning of warnings and symbols DANGER Indicates a situation that results in death or serious injury DANGER RISK OF ELECTROCUTION Indicates a situation that could result in electrocution DANGER RISK...

Страница 7: ...contact your dealer DANGER RISK OF BURNING SCALDING Do NOT touch the refrigerant piping water piping or internal parts during and immediately after operation It could be too hot or too cold Give it ti...

Страница 8: ...spital Name address and day and night telephone numbers for obtaining service In Europe EN378 provides the necessary guidance for this logbook 2 2 2 Installation site Provide sufficient space around t...

Страница 9: ...ices which may be a potential ignition source are installed in the duct work example hot surfaces with a temperature exceeding 700 C and electric switching device only auxiliary devices approved by th...

Страница 10: ...arage machinery room NOTICE Pipework shall be protected from physical damage Installation of pipework shall be kept to a minimum To determine the minimum floor area 1 Determine the total refrigerant c...

Страница 11: ...10 1 7 6 36 6 4 0 136 7 6 492 4 2 11 2 7 8 38 5 4 2 150 7 8 518 4 4 12 3 4 4 165 m kg Amin m2 4 6 20 0 4 8 21 8 5 0 23 6 1 842 5 2 25 6 1 843 4 45 5 4 27 6 2 0 4 83 5 6 29 7 2 2 5 31 5 8 31 8 2 4 5 7...

Страница 12: ...NOT release them directly into the environment Use a vacuum pump to evacuate the installation NOTICE After all the piping has been connected make sure there is no gas leak Use nitrogen to perform a g...

Страница 13: ...rant Possible consequence Incorrect refrigerant amount 2 2 4 Electrical DANGER RISK OF ELECTROCUTION Turn OFF all power supply before removing the switch box cover connecting electrical wiring or touc...

Страница 14: ...ctor CAUTION When connecting the power supply connect the earth cable first before making the current carrying connections When disconnecting the power supply disconnect the current carrying cables fi...

Страница 15: ...ble if the power supply is three phase and the compressor has an ON OFF starting method If there exists the possibility of reversed phase after a momentary black out and the power goes ON and OFF whil...

Страница 16: ...thout continuously operating ignition sources example open flames an operating gas appliance or an operating electric heater Connecting the refrigerant piping see 7 2 Connecting the refrigerant piping...

Страница 17: ...e refrigerant inside the unit is mildly flammable but normally does NOT leak If the refrigerant leaks in the room and comes in contact with fire from a burner a heater or a cooker this may result in f...

Страница 18: ...y can cause overheating electrical shock or fire Do NOT install a phase advancing capacitor because this unit is equipped with an inverter A phase advancing capacitor will reduce performance and may c...

Страница 19: ...BURNING SCALDING CAUTION Do NOT perform the test operation while working on the indoor units When performing the test operation NOT ONLY the outdoor unit but the connected indoor unit will operate as...

Страница 20: ...nds Troubleshooting see Troubleshooting DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING SCALDING WARNING When carrying out an inspection on the switch box of the unit ALWAYS make sure that the uni...

Страница 21: ...At delivery the unit MUST be checked for damage Any damage MUST be reported immediately to the claims agent of the carrier Bring the packed unit as close as possible to its final installation position...

Страница 22: ...t 1 3 2 2 1 Remove the accessories located at the bottom of the package 2 2 2 1 1 1 1 1 1 e d b a c f g h i a Installation manual b Operation manual c General safety precautions d Indoor unit fixing s...

Страница 23: ...ion cable e Insulation tape 5 2 Operation range Use the system in the following temperature and humidity ranges for safe and effective operation Operation mode Operation range Cooling a b Outdoor temp...

Страница 24: ...n and out of the site Do NOT install the unit in places often used as work place In case of construction works e g grinding works where a lot of dust is created the unit MUST be covered WARNING The ap...

Страница 25: ...lights It is NOT recommended to install the unit in the following places because it may shorten the life of the unit Where the voltage fluctuates a lot In vehicles or vessels Where acidic or alkaline...

Страница 26: ...lign the shafts with the slots and push them all the way in 2 Close the front panel slowly press at both sides and at the centre 6 2 3 To remove the front grille CAUTION Wear adequate personal protect...

Страница 27: ...panel 6 2 5 To remove the electrical wiring box cover 1 Remove the front grille 2 Remove 1 screw from the electrical wiring box 3 Open the electrical wiring box cover by pulling the protruding part on...

Страница 28: ...e on the wall using M4 25L screws field supply INFORMATION The removed pipe port cover can be kept in the mounting plate pocket 337 770 A 285 44 5 170 48 48 44 5 116 5 1 17 337 50 213 237 170 A d e mm...

Страница 29: ...in piping do NOT forget to seal the gap with putty 6 3 4 To remove the pipe port cover INFORMATION To connect the piping on right side right bottom left side or left bottom the pipe port cover MUST be...

Страница 30: ...orget to use a heat insulation tube on the indoor section of the extension hose a a b c 16 16 a Drain hose supplied with the indoor unit b Heat insulation tube field supply c Extension drain hose Ridg...

Страница 31: ...ove the pipe port cover here for right side piping b Remove the pipe port cover here for right bottom piping To connect the piping on left side left back or left bottom INFORMATION The factory default...

Страница 32: ...ain hose to the refrigerant piping bottom side using adhesive vinyl tape A B C b a A Left side piping B Left back piping C Left bottom piping a Remove the pipe port cover here for left side piping b R...

Страница 33: ...FORMATION Also read the precautions and requirements in the 2 General safety precautions 46 NOTICE The piping and other pressure containing parts shall be suitable for refrigerant Use phosphoric acid...

Страница 34: ...e thickness of the insulation materials should be at least 20 mm to prevent condensation on the surface of the insulation 7 2 Connecting the refrigerant piping 7 2 1 About connecting the refrigerant p...

Страница 35: ...stand the pressure and to prevent foreign materials e g mineral oils and moisture from mixing into the system Install the piping so that the flare is NOT subjected to mechanical stress Protect the pip...

Страница 36: ...4 Pipe bending guidelines Use a pipe bender for bending All pipe bends should be as gentle as possible bending radius should be 30 40 mm or larger 7 2 5 To flare the pipe end NOTICE Incomplete flarin...

Страница 37: ...the flare nut is fitted 7 2 6 To connect the refrigerant piping to the indoor unit WARNING MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable Pipe length Keep refrigerant p...

Страница 38: ...ply system complies with the electrical specifications of the units 2 Connecting the electrical wiring to the outdoor unit 3 Connecting the electrical wiring to the indoor unit 4 Connecting the main p...

Страница 39: ...ing the electrical wiring Keep the following in mind If stranded conductor wires are used install a round crimp style terminal on the end of the wire Place the round crimp style terminal on the wire u...

Страница 40: ...ing plate accessory b Interconnection cable c Wire guide 2 Open the front panel and then the service cover Refer to 6 2 Opening the indoor unit 425 3 Pass the interconnection cable from the outdoor un...

Страница 41: ...mm 6 Match wire colours with terminal numbers on the indoor unit terminal blocks and firmly screw the wires to the corresponding terminals 7 Connect the earth wire to the corresponding terminal 8 Fir...

Страница 42: ...r using insulation tape Overlap at least half the width of the tape with each turn d e c b f a 2 a Drain hose b Interconnection cable c Mounting plate accessory d Refrigerant piping e Indoor unit fixi...

Страница 43: ...on the mounting plate hooks Use the marks as a guide 2 Press the bottom frame of the unit with both hands to set it on the bottom hooks of the mounting plate Make sure that the wires do NOT get squee...

Страница 44: ...age any of the surrounding parts when cutting the address jumper 3 Turn the power supply on Result The flap of the indoor unit will open and close to set the reference position INFORMATION For FTXF an...

Страница 45: ...ss the indoor unit ON OFF switch while the operation lamp is blinking Jumper Address Factory setting 1 After cutting with nippers 2 INFORMATION If the setting could NOT be completed while the operatio...

Страница 46: ...that the air inlet and outlet of the unit is NOT obstructed by paper sheets cardboard or any other material There are NO missing phases or reversed phases The refrigerant pipes gas and liquid are the...

Страница 47: ...hed set the temperature to a normal level In cooling mode 26 28 C in heating mode 20 24 C 3 The system stops operating 3 minutes after the unit is turned OFF 11 3 1 To perform a test run in winter sea...

Страница 48: ...roperly please make sure the following is clear for the user Make sure that the user has the printed documentation and ask him her to keep it for future reference Inform the user that he can find the...

Страница 49: ...oner 4P519439 16R 2021 12 13 Disposal NOTICE Do NOT try to dismantle the system yourself dismantling of the system treatment of the refrigerant oil and other parts MUST comply with applicable legislat...

Страница 50: ...or applied parts and numbering refer to the wiring diagram on the unit Part numbering is by Arabic numbers in ascending order for each part and is represented in the overview below by in the part code...

Страница 51: ...ness H P LED V L Pilot lamp light emitting diode HAP Light emitting diode service monitor green HIGH VOLTAGE High voltage IES Intelligent eye sensor IPM Intelligent power module K R KCR KFR KHuR K M M...

Страница 52: ...ssure sensor high S NPL Pressure sensor low S PH HPS Pressure switch high S PL Pressure switch low S T Thermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge arrester SR WLU Signal recei...

Страница 53: ...duct or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance inst...

Страница 54: ......

Страница 55: ......

Страница 56: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 4P519439 16R 2021 12 Copyright 2...

Отзывы: