Databook Modular T - October 2022 - Rev. 00
20
4.11.2.
Smart Version
In accordance with the image here below showed, adding a pre-electrical heater (ATD**HEFBU) is mandatory
for outdoor temperature lower than -5°C for either tackling or preventing frost issue.
The unit has been equipped with a differential pressure switch to prevent a possible risk of icing at heat
exchanger level. Depending on the working condition, the installer must adjust the setting according the
charts below.
Temp
Lim
it
Main Module
ATB*S / SB.ATB*S
10
0
-10
-5
-15
45
…
-20
Main Module
ATB*S
SB.ATB*S
Preheating electric coil
ATD*HEFBU
Outdoor Temperature (°C)