SiBE041134EB
Forced Cooling Operation
Trial Operation and Field Settings
107
2. Forced Cooling Operation
Indoor Unit
Outdoor Unit: RXS20/25K2V1B, RXS20/25K3V1B, RXS20/25L2V1B, ARXS25L2V1B
Caution
When pressing the button, do not touch the terminal board. It has a high voltage and may cause
electric shock.
Item
Forced Cooling
Conditions
The forced cooling operation is allowed when both of the following conditions are
met.
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
Start
The forced cooling operation starts when any of the following conditions are fulfilled.
1) Press the forced cooling operation
ON/OFF
button (SW1) on the indoor unit for 5
seconds.
2) Press the forced cooling operation
ON/OFF
button (SW1) on the outdoor unit
within around 3 minutes after power is supplied. (RXS20/25K2V1B, RXS20/
25K3V1B, RXS20/25L2V1B, ARXS25L2V1B only)
Command
frequency
58 Hz
End
The forced cooling operation ends when any of the following conditions are fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced cooling operation
ON/OFF
button (SW1) on the indoor unit again.
3) Press the
ON/OFF
button on the remote controller.
4) Press the forced cooling operation
ON/OFF
button (SW1) on the outdoor unit.
(RXS20/25K2V1B, RXS20/25K3V1B, RXS20/25L2V1B, ARXS25L2V1B only)
Others
Protection functions have priority over all other functions during forced cooling
operation.
ON/OFF
button
(R22767)
1
2
3
Push here
Screwdriver
(R22528)
Forced cooling
operation ON/OFF
button