SiBE04-809
Troubleshooting
Service Diagnosis
99
4.18
Compressor System Sensor
Abnormality
Remote
Controller
Display
H0
Method of
Malfunction
Detection
The system checks the DC current before the compressor starts.
Malfunction
Decision
Conditions
If the DC current before compressor start-up is out of the range 0.5-4.5 V (sensor output
converted to voltage value) or if the DC voltage before compressor start-up is below 50 V.
Supposed
Causes
PCB defective
Broken or poorly connected harness
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
(R8310)
YES
Turn off the power and turn it on
again.
YES
NO
Replace the harness.
No problem.
Keep on running.
Replace the PCB.
Is the harness broken?
Get restarted and error
displayed again?
Check the harness S30.
Содержание ARXG35E3V1B
Страница 1: ...SiBE04 809 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type E Series...
Страница 11: ...Introduction SiBE04 809 x...
Страница 12: ...SiBE04 809 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 14: ...SiBE04 809 Specifications 3 Part 2 Specifications 1 Specifications 4...
Страница 23: ...Printed Circuit Board Connector Wiring Diagram SiBE04 809 12 Printed Circuit Board Connector Wiring Diagram...
Страница 207: ...Wiring Diagrams SiBE04 809 196 Appendix...