SiBE04-809
Troubleshooting
Service Diagnosis
107
4.23
Radiation Fin Temperature Rise
Remote
Controller
Display
L4
Method of
Malfunction
Detection
A radiation fin temperature rise is detected by checking the radiation fin thermistor with the
compressor on.
Malfunction
Decision
Conditions
If the radiation fin temperature with the compressor on is above 90°C.
Clearing condition : when the temperature drops below 85°C.
If a radiation fin temperature rise takes place 4 times successively, the system will be shut
down.
The error counter will reset itself if this or any other error does not occur during the following
60-minute compressor running time (total time).
Supposed
Causes
Fin temperature rise due to defective outdoor unit fan
Fin temperature rise due to short-circuit
Fin thermistor defective
Connector in poor contact
Outdoor unit PCB defective
Silicon grease is not applied properly on the heat radiation fin after replacing outdoor unit
PCB
Содержание ARXG25E3V1B
Страница 1: ...SiBE04 809 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type E Series ...
Страница 11: ...Introduction SiBE04 809 x ...
Страница 12: ...SiBE04 809 List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Страница 14: ...SiBE04 809 Specifications 3 Part 2 Specifications 1 Specifications 4 ...
Страница 23: ...Printed Circuit Board Connector Wiring Diagram SiBE04 809 12 Printed Circuit Board Connector Wiring Diagram ...
Страница 207: ...Wiring Diagrams SiBE04 809 196 Appendix ...