Control Specification
SiBE041525F
35
Functions and Control
3.10 Defrost Control
Outline
Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor
heat exchanger temperature must be more than a certain value to finish defrosting.
Detail
Conditions for Starting Defrost
The starting conditions are determined with the outdoor temperature and the outdoor heat
exchanger temperature.
The system is in heating operation.
The compressor operates for 6 minutes.
More than
A
minutes of accumulated time have passed since the start of the operation, or
ending the previous defrosting.
Conditions for Canceling Defrost
The judgment is made with the outdoor heat exchanger temperature. (
B
°C)
.
: The same value continues.
20/25 class
35 class
50 class
60/71 class
A
(minute)
28
28
25
25
B
(°C)
4-22
4-22
6-30
6-30
C
(Hz)
74
74
48
48
D
(Hz)
74
74
42
42
E
(seconds)
80
80
60
60
F
(seconds)
60
60
60
60
G
(seconds)
630
630
460
460
H
(seconds)
100
70
60
90
J
(seconds)
5
5
8
8
K
(pulse)
450
450
450
450
L
(pulse)
280-380
280-380
300-450
300-450
M
(pulse)
450
450
200
200
Frequency
Compressor
Four way valve
Fan
ON
OFF
ON
OFF
ON
OFF
0 Hz
0 Hz
C
Hz
D
Hz
5 sec.
PI control
J
sec.
H
sec.
(R23076)
E
sec.
F
sec.
G
sec.
L
pulse zone
Electronic
expansion valve
opening
Normal
control
K
pulse
zone
M
pulse
zone
Starting
control
Содержание ARX20K2V1B
Страница 12: ...SiBE041525F 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 15: ...SiBE041525F Specifications 4 Part 2 Specifications 1 Specifications 5 ...
Страница 16: ...Specifications SiBE041525F 5 Specifications 1 Specifications See corresponding databook ...
Страница 51: ...SiBE041525F Remote Controller 40 Part 5 Remote Controller 1 Remote Controller 41 ...