IM 1083-3
10 www.DaikinApplied.com
Louver Installation With Typical Unit
Arrangements – 16⅝" Unit Depth
Figure 10:
The 16⅝˝ (422mm) deep unit with open
refrigerant pipe chase and floor level outdoor intake louver
location
Intake Louver
Floor
Line
Unit Refrigerant Piping
Important:
Gasket sealing
surface is required.
Sealed Cement
Mortar; Pitch
Away From Unit
Lintel
(By Others)
1"
(25mm)
Figure 11:
16⅝" (422mm) deep unit with open refrigerant
pipe chase & above-floor-level outdoor intake louver
application with chased wall
Intake Louver
Floor
Line
Not Less
Than 3"
Not More
Than 21"
Unit Refrigerant Piping
Important:
Gasket sealing
surface is required.
Sealed Cement
Mortar; Pitch
Away From Unit
Lintel (By Others)
1"
(25mm)
CAUTION
Accumulated moisture can cause property damage if not properly
drained. Installing contractor must provide such drainage.
Figure 12: Above floor level outdoor air intake with
accessory closed refrigerant pipe chase
Unit Refrigerant Piping
Floor Line
Lintel (By Others)
Intake Louver
Not Less Than 3"
Not More
Than 28"
Insulated Closure
Plate Accessory
Provide
Drainage
Important:
Gasket sealing
surface is required.
Sealed Cement
Mortar; Pitch Away
From Unit
1"
(25mm)
Figure 13: Floor level outdoor air intake with window
below unit top and 9˝ “finished” (painted) accessory
(insulated) closed refrigerant pipe chase
Lintel (By Others)
Intake Louver
Important:
Gasket sealing
surface is required.
Sash
Unit Refrigerant Piping
Painted, Insulated Closure Plate Accessory
Floor Line
Sealed Cement
Mortar;Pitch Away
From Unit
1"
(25mm)