16
|
Disposal
Installer reference guide
248
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
16.1.3 Recovery mode — In case of 3N~ models (7-segments display)
Before recovering refrigerant, make sure the electronic expansion valves are open.
When power is ON, this has to be done by using the recovery mode.
Components
To activate/deactivate the recovery mode, you need the following components:
3N~
BS1
BS2
BS3
7‑segments display
BS1~BS3
Push buttons. Operate the push buttons with an insulated stick (such as a closed
ballpoint pen) to avoid touching of live parts.
To activate the recovery mode
INFORMATION
If you get confused in the middle of the process, press BS1 to return to the default
situation.
Before recovering refrigerant, activate the recovery mode as follows:
#
Action
7-segments display
(a)
1
Start from the default situation.
2
Select mode 2.
Press and hold
BS1
for 5 seconds.
3
Select setting 9.
Press
BS2
9 times.
4
Select value 2.
Содержание ALTHERMA