9
|
Electrical installation
Installer reference guide
106
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
4P620241-1 – 2020.06
1 2
X5M
4
Fix the cables with cable ties to the cable tie mountings.
Bypass valve kit necessity
For reversible systems (cooling) in which an external backup heater kit is
installed, the installation of valve kit EKMBHBP1 is required if condensation is
expected inside the backup heater.
7
10
13
16
19
22
25
28
31
7
10
13
16
19
22
25
28
31
20
23
26
29
32
A (°C)
A (°C)
B (°C DB)
A
Leaving water evaporator temperature
B
Dry-bulb temperature
Relative humidity 40%
Relative humidity 60%
Relative humidity 80%
Example:
Given are an ambient temperature of 25°C and a relative humidity of
40%. If the leaving water evaporator temperature is <12°C, condensation will
occur.
Note:
See the psychrometric chart for more information.
Содержание ALTHERMA
Страница 277: ...11 11 ...
Страница 278: ......
Страница 279: ......
Страница 280: ...4P620241 1 2020 06 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...