14.3 To start and stop forced cooling
1
Turn OFF the power.
2
Remove the service cover and the switch box cover.
3
Remove the service PCB switch cover.
4
Set DIP switch SW5 and SW6 to OFF.
5
Set DIP switch SW2 to COOL.
4
3
2
1
2
1
4
3
2
1
2
1
HEAT
COOL
A
1
2
3
4
5
2
3
SW5
SW6
SW2
OFF
ON
1×
1
6
Reattach the service PCB switch cover, switch box cover and service cover.
7
Turn ON the outdoor unit.
8
Press the forced cooling operation switch SW1 to begin forced cooling.
9
Press the forced cooling operation switch SW1 to stop forced cooling.