Special Control
ESIE09-08A
58
Function
3. Special Control
3.1
Startup Control
This control is used to equalize the pressure in the front and back of the compressor prior to the startup of the compressor, thus
reducing startup loads. Furthermore, the inverter is turned ON to charge the capacitor.
In addition, to avoid stresses to the compressor after the startup, the following control is made and the position of the four way valve
is also determined. To position the four way valve, the master and slave units simultaneously start up.
3.1.1
Startup Control in Heating Operation
* Always after POWER ON/OFF, compressor frequency is limited. This is not the case after thermo ON/OFF/ON.
Remark:
A thermostat ON demand will activate the outdoor fan, followed by the outdoor compressor and finally indoor
compressor.
Outdoor
Thermostat ON
Pressure equalization control
prior to startup
Startup control
STEP1
STEP2
Compressor
0 Hz
57 Hz Unload
57 Hz Unload
+2 steps/20 sec.
(until Pc - Pe>0.39MPa is achieved)
Outdoor unit fan
From starting
~ 1 min. : STEP 7
1 ~ 3 min. : STEP 3
3 ~ 5 min. : OFF
STEP8
STEP8
Four way valve
Holds
ON
ON
Main electronic expansion
valve (EV1)
0 pls
0 pls
0 pls
Subcooling electronic
expansion valve (EV3)
0 pls
0 pls
0 pls
Hot gas bypass valve (SVP)
OFF
OFF
OFF
Ending conditions
Pc - Pe<0.3MPa
A lapse of 1 to 5 min.
A lapse of 10 sec.
A lapse of 130 sec.
Pc>2.70MPa
Pc - Pe>0.39MPa
OR
OR
Indoor
STEP1
STEP2
Indoor compressor
First 10 minutes -> maximum 128 Hz*
To maximum frequency
4-way valve
OFF
OFF
Pump
HOT START
High pressure side > 14 bar
Maximum 5 minutes
Gradual to PI control
OR
Содержание ALTHERMA HT EKBUHAA6 V3
Страница 2: ......
Страница 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Страница 13: ...ESIE09 08A General Information 1 Part 1 General Information 1 Model Names of Indoor Outdoor Units Tanks 2 ...
Страница 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Страница 17: ...ESIE09 08A Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Unit 8 ...
Страница 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Страница 38: ...Functional Parts Layout ESIE09 08A 26 Refrigerant Circuit 2 6 EKHTSU 200 260 A AB AC Front view Tank sensor ...
Страница 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Страница 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Страница 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Страница 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Страница 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Страница 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Страница 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Страница 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Страница 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Страница 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Страница 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...
Страница 266: ...Method of Replacing the Inverter s Power Transistors Modules ESIE09 08A 256 Appendix Inverter PC board C C W U V ...
Страница 288: ...3 Way Valve ESIE09 08A 278 Appendix ...