ESIE09-08A
Troubleshooting by Indication on the Remote Controller
Troubleshooting
153
3.10
“CA”
Indoor Unit: Leaving Water Thermistor Error (R5T)
Remote Control
Display
CA
Subcode 0
Applicable Models
AII indoor unit models
Method of
Malfunction
Detection
Malfunction detection is carried out by temperature detected by leaving water temperature thermistor.
Malfunction
Decision Conditions
When the leaving water temperature thermistor becomes disconnected or shorted while the unit is
running.
Supposed Causes
Defect of indoor unit thermistor for leaving water (R5T)
Defect of indoor unit PC board (A1P)
Troubleshooting
Refer to thermistor resistance / temperature characteristics table on P251.
Caution
Be sure to turn off power switch before connecting or disconnecting connector,
otherwise parts may be damaged.
Replace the indoor unit PC board (A1P).
Connect the thermistor and turn
on again.
NO
NO
Replace the thermistor
(R5T).
YES
YES
Connector
(X17A) is connected to
the indoor unit PC
board.
Resistance
is normal when
measured after
disconnecting the thermistor
(X17A) from the indoor unit
PC board.
(7.2k ~112k )
(V2786)
Faulty thermistor
value > 95 C
Bad wire connection
value < -43.6 C
Содержание ALTHERMA HT EKBUHAA6 V3
Страница 2: ......
Страница 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Страница 13: ...ESIE09 08A General Information 1 Part 1 General Information 1 Model Names of Indoor Outdoor Units Tanks 2 ...
Страница 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Страница 17: ...ESIE09 08A Specifications 5 Part 2 Specifications 1 Specifications 6 1 1 Outdoor Units 6 1 2 Indoor Unit 8 ...
Страница 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Страница 38: ...Functional Parts Layout ESIE09 08A 26 Refrigerant Circuit 2 6 EKHTSU 200 260 A AB AC Front view Tank sensor ...
Страница 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Страница 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Страница 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Страница 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Страница 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Страница 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Страница 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Страница 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Страница 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Страница 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Страница 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...
Страница 266: ...Method of Replacing the Inverter s Power Transistors Modules ESIE09 08A 256 Appendix Inverter PC board C C W U V ...
Страница 288: ...3 Way Valve ESIE09 08A 278 Appendix ...