Altherma by Daikin
Correct Installation Of The ESBE 3 Port Valve
Supplied By Daikin For Domestic Hot Water
Страница 1: ...Public Altherma by Daikin Correct Installation Of The ESBE 3 Port Valve Supplied By Daikin For Domestic Hot Water ...
Страница 2: ... wiring can be altered from the valve to force the correct valve operation For some Honeywell mid position valves the white and grey can be linked to enable this operation If the installer has fitted the wrong valve it is up to them to make enquires with the manufacturer of the valve about re wiring From July 2008 Daikin have started supplying there own valve to eliminate this confusion on site Th...
Страница 3: ...ESBE 3 port Valve Installation Altherma ESBE 3 Port Valve UKEIOE3PV 05 09 Page 3 ...
Страница 4: ...nsure that the jumper connections are installed as per mechanical configuration that the valve body is installed in Altherma ESBE 3 Port Valve UKEIOE3PV 05 09 Page 4 Lift tab on front of valve to expose the main fixing screw to remove ESBE motor ...
Страница 5: ... the picture Then fit the motor holding pin at position 5 if installed this way After this fit the motor to the valve body and secure with the centre pin Altherma ESBE 3 Port Valve UKEIOE3PV 05 09 Page 5 Finally set the jumper pins as shown on the previous page when the motor is powered up for the first time you need to ensure that you change the jumper pins so that the white blocking pointer moto...
Страница 6: ...ESBE 3 port Valve Installation Altherma ESBE 3 Port Valve UKEIOE3PV 05 09 Page 6 ...