12 Troubleshooting
Installer reference guide
73
EPGA11~ EA9W
Daikin Altherma – Low temperature split
4P556075-1 – 2019.02
12.3
Solving problems based on
symptoms
12.3.1
Symptom: The unit is NOT heating or
cooling as expected
12.3.2
Symptom: Hot water does NOT reach the
desired temperature
Possible causes
Corrective action
One of the tank temperature
sensors is broken.
See the service manual of the
unit for the corresponding
corrective action.
12.3.3
Symptom: The compressor does NOT
start (space heating or domestic water
heating)
Possible causes
Corrective action
The unit must start up out of its
operation range (the water
temperature is too low)
If the water temperature is too
low, the unit uses the backup
heater to reach the minimum
water temperature first (15°C).
Check and make sure that:
▪ The power supply to the
backup heater is correctly
wired.
▪ The backup heater thermal
protector is NOT activated.
▪ The backup heater contactor is
NOT broken.
If the problem persists after you
have conducted all of the above
checks, contact your dealer.
The preferential kWh rate power
supply settings and electrical
connections do NOT match
This should match with the
connections as explained in
"6.4 Preparing electrical
wiring" on page 21
connect the main power
supply" on page 33
.
The preferential kWh rate signal
was sent by the electricity
company
Wait for the power to return (2
hours max.).
12.3.4
Symptom: The system is making gurgling
noises after commissioning
Possible cause
Corrective action
There is air in the system.
Purge air from the system.
(a)
Various malfunctions.
Check if
or
is displayed
on the home screen of the user
interface. See
the help text in case of a
malfunction" on page 75
more information about the
malfunction.
(a)
We recommend to purge air with the unit's air purge
function (to be performed by the installer). If you purge air
from the heat emitters or collectors, mind the following:
WARNING
Air purging heat emitters or collectors.
Before you
purge air from heat emitters or collectors, check if
or
is displayed on the home screen of the user interface.
▪ If not, you can purge air immediately.
▪ If yes, make sure that the room where you want to
purge air is sufficiently ventilated.
Reason:
Refrigerant
might leak into the water circuit, and subsequently into
the room when you purge air from the heat emitters or
collectors.
12.3.5
Symptom: The pump is making noise
(cavitation)
Possible causes
Corrective action
There is air in the system
Purge air manually on both
zones (see
) or use the
automatic air purge function on
both zones (see
automatic air purge" on page 67
The water pressure at the pump
inlet is too low
Check and make sure that:
▪ The water pressure is >1 bar.
▪ The water pressure sensor is
not broken.
▪ The expansion vessel is NOT
broken.
▪ The valve (if equipped) of the
water
circuit
towards
the
expansion vessel is open.
▪ The pre-pressure setting of the
expansion vessel is correct
(see
pressure of the expansion
vessel" on page 21
12.3.6
Symptom: The pressure relief valve opens
Possible causes
Corrective action
The expansion vessel is broken
Replace the expansion vessel.
The valve (if equipped) of the
water circuit towards the
expansion vessel is closed.
Open the valve.
The water volume in the
installation is too high
Make sure that the water volume
in the installation is below the
maximum allowed value (see
"6.3.3 To check the water volume
and flow rate" on page 20
"6.3.4 Changing the pre-pressure
of the expansion vessel" on
page 21
The water circuit head is too high The water circuit head is the
difference in height between the
indoor unit and the highest point
of the water circuit. If the indoor
unit is located at the highest
point of the installation, the
installation height is considered
0 m. The maximum water circuit
head is 10 m.
Check the installation
requirements.