8 Configuration
Installer reference guide
60
EPGA11~ EABH/9W
Daikin Altherma – Low temperature split
4P556069-1 – 2018.10
About energy prices in case of an incentive per kWh renewable
energy
An incentive can be taken into account when setting the energy
prices. Although the running cost can increase, the total operation
cost, taking into account the reimbursement will be optimized.
NOTICE
Make sure to modify the setting of the energy prices at the
end of the incentive period.
To set the gas price in case of an incentive per kWh renewable
energy
Calculate the value for the gas price with the following formula:
▪ Actual gas price+(Incentive/kWh×0.9)
For the procedure to set the gas price, see
.
To set the electricity price in case of an incentive per kWh
renewable energy
Calculate the value for the electricity price with following formula:
▪ Actual electricity price+Incentive/kWh
For the procedure to set the electricity price, see
Example
This is an example and the prices and/or values used in this
example are NOT accurate.
Data
Price/kWh
Gas price
4.08
Electricity price
12.49
Renewable heat incentive per
kWh
5
Calculation of the gas price:
Gas price=Actual gas price+(Incentive/kWh×0.9)
Gas price=4.08+(5×0.9)
Gas price=8.58
Calculation of the electricity price:
Electricity price=Actual electricity price+Incentive/kWh
Electricity price=12.49+5
Electricity price=17.49
Price
Value in breadcrumb
Gas: 4.08 /kWh
[7.6]=8.6
Electricity: 12.49 /kWh
[7.5.1]=17
8.4.8
Information
Dealer information
The installer can fill in his contact number here.
#
Code
Description
[8.3]
N/A
Number that users can call in case of
problems.
Possible read-out information
In menu…
You can read out…
[8.1] Energy data
Produced energy, consumed
electricity, and consumed gas
[8.2] Malfunction history
Malfunction history
[8.3] Dealer information
Contact/helpdesk number
In menu…
You can read out…
[8.4] Sensors
Room, tank or domestic hot
water, outside, and leaving water
temperature (if applicable)
[8.5] Actuators
Status/mode of each actuator
Example:
Domestic hot water
pump ON/OFF
[8.6] Operation modes
Current operation mode
Example:
Defrost/oil return
mode
[8.7] About
Version information about the
system
[8.8] Connection status
Information about the connection
status of the unit, the room
thermostat and the LAN adapter.
8.4.9
Installer settings
Configuration wizard
After first power ON of the system, the user interface will guide you
using the configuration wizard. This way you can set the most
important initial settings. This way the unit will be able to run
properly. Afterwards, more detailed settings can be done via the
menu structure if required.
To restart the configuration wizard, go to Installer settings >
Configuration wizard [9.1].
Domestic hot water
This part only applies to systems with an optional domestic hot water
tank installed.
Domestic hot water
The following setting determines if the system can prepare domestic
hot water or not, and which tank is used. Set this setting according to
the actual installation.
#
Code
Description
[9.2.1]
[E‑05]
(*)
[E‑06]
(*)
[E‑07]
(*)
▪ No DHW
No tank installed.
▪ EKHWS/E
Tank with booster heater installed at
the side of the tank.
▪ EKHWP/HYC
Tank with optional booster heater
installed at the top of the tank.
(*)
Use the menu structure instead of the overview settings.
Menu structure setting [9.2.1] replaces the following 3
overview settings:
[E-05]
Can the system prepare domestic hot water?
[E-06]
Is a domestic hot water tank installed in the system?
[E-07]
What kind of domestic hot water tank is installed?
In case of a third-party tank, we recommend to use the setting for
EKHWS.
In case of EKHWP/HYC, we recommend to set the temperature of
the booster heater NOT higher than 70°C.