8 Configuration
Installer reference guide
58
EPGA11~ EABH/9W
Daikin Altherma – Low temperature split
4P556069-1 – 2018.10
In case of Reheat only domestic hot water preparation, the desired
tank temperature is weather dependent (according to the weather
dependent curve). During weather dependent operation, the end-
user cannot adjust the desired tank temperature on the user
interface. Also see
"8.3.7 Detailed screen with weather-dependent
#
Code
Description
[5.C]
[0-0E]
[0-0D]
[0-0C]
[0-0B]
Weather-dependent curve
T
DHW
T
a
[0-0C]
[0-0B]
[0-0E]
[0-0D]
▪ T
DHW
: The desired tank temperature.
▪ T
a
: The (averaged) outdoor ambient
temperature
▪ [0-0E]:
low
outdoor
ambient
temperature: -40°C‑5°C
▪ [0-0D]:
high
outdoor
ambient
temperature: 10°C‑25°C
▪ [0-0C]: desired tank temperature when
the outdoor temperature equals or
drops
below
the
low
ambient
temperature: 45°C~[6‑0E]°C
▪ [0-0B]: desired tank temperature when
the outdoor temperature equals or
rises
above
the
high
ambient
temperature: 35°C~[6‑0E]°C
Margin
In domestic hot water operation, the following hysteresis value can
be set for the heat pump operation:
#
Code
Description
[5.D]
[6-01]
The temperature difference determining
the heat pump OFF temperature.
Range: 0°C~10°C
Example: setpoint (T
U
)>maximum heat pump temperature–[6‑01]
(T
HP MAX
–[6‑01])
t
T
DHW
T
HP ON
T
HP OFF
T
HP MAX
T
U
=
T
BUH OFF
[6-01]
[6-00]
T
U
= 60°C
T
HP MAX
= 50°C
[6-01] = 2°C
[6-00] = 2°C
HP
BUH
HP
5
10
20
30
40
46
48
50
60
BUH
Backup heater
HP
Heat pump. If heating up time by the heat pump takes too
long, auxiliary heating by the backup heater can take place
T
BUH OFF
Backup heater OFF temperature (T
U
)
T
HP MAX
Maximum heat pump temperature at sensor in domestic
hot water tank
T
HP OFF
Heat pump OFF temperature (T
HP MAX
−[6-01])
T
HP ON
Heat pump ON temperature (T
HP OFF
−[6-00])
T
DHW
Domestic hot water temperature
T
U
User set point temperature (as set on the user interface)
t
Time
Example: setpoint (T
U
)≤maximum heat pump temperature–[6‑01]
(T
HP MAX
–[6‑01])
t
[6-00]
HP
5
10
20
30
40
43
45
T
U
=T
HP OFF
T
HP MAX
T
DHW
T
HP ON
50
HP
Heat pump. If heating up time by the heat pump takes too
long, auxiliary heating by the backup heater can take place
T
HP MAX
Maximum heat pump temperature at sensor in domestic
hot water tank
T
HP OFF
Heat pump OFF temperature (T
HP MAX
−[6-01])
T
HP ON
Heat pump ON temperature (T
HP OFF
−[6-00])
T
DHW
Domestic hot water temperature
T
U
User set point temperature (as set on the user interface)
t
Time
INFORMATION
The maximum heat pump temperature depends on the
ambient temperature. For more information, see the
operation range.
8.4.7
User settings
Language
#
Code
Description
[7.1]
N/A
Language
Time/date
#
Code
Description
[7.2]
N/A
Set the local time and date
INFORMATION
By default, daylight savings time is enabled and clock
format is set to 24 hours. If you want to change these
settings, you can do this in the menu structure (User
settings > Time/date) once the unit is initialised.
Holiday
About holiday mode
During your holiday, you can use the holiday mode to deviate from
your normal schedules without having to change them. While holiday
mode is active, space heating/cooling operation and domestic hot
water operation will be turned off. Room frost protection and anti-
legionella operation will remain active.
Typical workflow
Using holiday mode typically consists of the following stages:
1
Setting the starting date and ending date of your holiday.
2
Activating the holiday mode.
To check if holiday mode is activated and/or running
If
is activated on the home screen, holiday mode is active.