7 Installation
Installation and operation manual
20
EHYKOMB33A
Daikin Altherma hybrid heat pump – gas boiler module
4P353067-1K – 2020.10
7
6
5
10
9
11
8
3
4
2
1
0
L2
L1
0
1
2
3
4
6
7
5
L2=–1.8×L1+11.8
Multi-boiler installation
INFORMATION
All piping lengths in the tables below are maximum
equivalent piping lengths.
L1
L1
C
83
C
43
C
43
6
L2
5
C
83
6
L1
C
43
C
43
5
5
5
L1
L2
L1
L1
L2
The horizontal flue MUST be installed under a 3° fall towards the
boiler (50 mm per metre) and MUST be supported with a minimum
of 1 bracket at each meter length. Best recommended position of the
bracket is just before the joint.
INFORMATION
Flexible flue gas lines may NOT be used in horizontal
connection sections.
INFORMATION
The maximum lengths in the table below apply to each gas
boiler separately.
C
83
(6)
C
43
(5)
Twin-80
60/100
80/125
Twin-80
L1+L2 (m)
L1 (m)
L1 (m)
L1+L2 (m)
80
10
29
80
Special remark regarding
C
83
:
See the table below for the
minimum diameters of the combined gas exhaust system.
Number of units
Minimum Ø
2
130
3
150
4
180
5
200
6
220
7
230
8
250
9
270
10
280
11
290
12
300
Special remark regarding
C
43
:
See the table below for the
minimum diameters of the combined gas exhaust/air intake system.
Number of
units
Concentric
Dual pipe
Gas
exhaust
Air intake
Gas
exhaust
Air intake
2
161
302
161
255
3
172
322
172
272
4
183
343
183
290
5
195
366
195
309
6
206
386
206
326
7
217
407
217
344
8
229
429
229
363
9
240
449
240
380
10
251
470
251
398
11
263
493
263
416
12
274
513
274
434
13
286
536
286
453
14
297
556
297
470
15
308
577
308
488
16
320
599
320
507
17
331
620
331
524
18
342
641
342
541
19
354
663
354
560
20
365
683
365
578
Special remark regarding
C
93
:
The minimum inner dimensions of
the chimney have to be 200×200 mm.
7.7.5
Applicable materials
Materials for the installation of the gas exhaust and/or air intake
MUST be bought according to the table below.
D BG BA
HR HU SK
SI
CZ
ES PT PL GR CY IE TR
MT LT
LT LV UK FR
B
Daikin
Daikin
Daikin
Daikin
Daikin
Daikin
(b) (a)
(a)
(a)
(b)
C
C
C
C
93
C
C
C
83
63
53
43
33
13
IT
CH AT
(b)
a
Gas exhaust/air intake parts can be bought from a third
party. All parts purchased from an external supplier
MUST comply with EN14471.