8 Configuration
Installer reference guide
57
ERGA04~08DAV3(A) + 08S23DAV
Daikin Altherma – Low temperature split
4P499573-1A – 2018.11
Heating WD curve
Set weather-dependent heating for the additional zone (if [3.4] = 1 or
2):
#
Code
Description
[3.5]
[0-00]
[0-01]
[0-02]
[0-03]
Set weather-dependent heating:
[0-00]
[0-01]
Ta
Tt
[0-03]
[0-02]
▪ T
t
: Target leaving water temperature
(additional zone)
▪ T
a
: Outdoor temperature
▪ [0-03]:
Low
outdoor
ambient
temperature. –40°C~+5°C
▪ [0-02]:
High
outdoor
ambient
temperature. 10°C~25°C
▪ [0-01]:
Desired
leaving
water
temperature
when
the
outdoor
temperature equals or drops below the
low
ambient
temperature.
[9‑05]°C~[9‑06]°C
Note:
This value should be higher
than [0‑00] as for low outdoor
temperatures
warmer
water
is
required.
▪ [0-00]:
Desired
leaving
water
temperature
when
the
outdoor
temperature equals or rises above the
high
ambient
temperature.
[9‑05]~min(45, [9‑06])°C
Note:
This value should be lower than
[0‑01]
as
for
high
outdoor
temperatures less warm water is
required.
Emitter type
For more info about this functionality, see
#
Code
Description
[3.7]
[2‑0D]
Emitter type
▪ 0: Underfloor heating
▪ 1: Fancoil unit
▪ 2: Radiator
The setting of the emitter type has an influence on the space heating
setpoint range and the target delta T in heating as follows:
Emitter type
Additional zone
Space heating
setpoint range
[9‑05]~[9‑06]
Target delta T in
heating [1‑0C]
0: Underfloor heating Maximum 55°C
Variable (see [2.B])
1: Fancoil unit
Maximum 55°C
Variable (see [2.B])
2: Radiator
Maximum 65°C
Fixed 10°C
Setpoint range
For more information about this setting, also see
.
#
Code
Description
Leaving water temperature range for the additional leaving water
temperature zone (= the leaving water temperature zone with the
highest leaving water temperature in heating operation)
[3.8.1]
[9-05]
Heating minimum: 15°C~37°C
[3.8.2]
[9-06]
Heating maximum
▪ [2‑0D]=2 (emitter type additional zone
= radiator)
37°C~65°C
▪ Else: 37°C~55°C
Control
The control type is displayed here, but cannot be adjusted. It is
determined by the control type of the main zone. For more info about
the functionality, see
.
#
Code
Description
[3.9]
N/A
Control
▪ Leaving water if the control type of the
main zone is Leaving water.
▪ External room thermostat if the control
type of the main zone is External room
thermostat or Room thermostat.
Thermostat type
Only applicable in external room thermostat control. For more info
about the functionality, see
#
Code
Description
[3.A]
[C‑06]
External room thermostat type for the
additional zone:
▪ 1: 1 contact. Connected to only 1
digital input (X2M/35a)
▪ 2: 2 contacts. Connected to 2 digital
inputs (X2M/34a and X2M/35a)
Leaving water temperature: Delta T
For more information, see
.
#
Code
Description
[3.B.1]
[1-0C]
Delta T heating: A minimum temperature
difference is required for the good
operation of heat emitters in heating
mode.
▪ If [2-0D] = 2, this is fixed to 10°C
▪ Else: 3°C~10°C
#
Code
Description
[3.B.1]
[1-0C]
Delta T heating: A minimum temperature
difference is required for the good
operation of heat emitters in heating
mode.
▪ If [2-0D] = 2, this is fixed to 8°C
▪ Else: 3°C~10°C
8.4.5
Space heating
About space operation modes
This unit is a heating only model. The system can heat up a space,
but NOT cool down a space.
Operation range
Depending on the average outdoor temperature, the operation of the
unit in space heating is prohibited.