7 Installation
Installer reference guide
41
ERLQ004~008CA + EHVH/X04+08S18+26CB
Daikin Altherma – Low temperature split
4P384973-1A – 2016.02
INFORMATION
To access the domestic hot water temperature sensor, the
switch box can be tilted. The switch box should NOT be
removed from the unit.
Routing
Possible cables (depending on unit type and installed options)
a
Low voltage
▪ Preferential power supply contact
▪ User interface
▪ Power consumption digital inputs (field supply)
▪ Outdoor ambient temperature sensor (option)
▪ Indoor ambient temperature sensor (option)
▪ Electrical meters (field supply)
b
High voltage power supply
▪ Interconnection cable
▪ Normal kWh rate power supply
▪ Preferential kWh rate power supply
▪ Power supply for backup heater
▪ Power supply for bottom plate heater (option)
c
High voltage control signal
▪ Heat pump convector (option)
▪ Room thermostat (option)
▪ Shut-off valve (field supply)
▪ Domestic hot water pump (field supply)
▪ Alarm output
▪ Changeover to external heat source control
▪ Space cool/heat operation control
CAUTION
Do NOT push or place redundant cable length in the unit.
7.9.7
To connect the main power supply
1
Connect the main power supply.
In case of normal kWh rate power supply
X1M
1 2 3
1 2 3
X2M
X5M
X6YB
X6YA
X6Y
X1A X19A
3031
a
Legend: see illustration below.
In case of preferential kWh rate power supply
Connect X6Y to X6YB.
X1M
1 2 3
1 2
L N
L N
3
X2M
X5M
X6YB
X6YA
X6Y
X1A
X19A
S1S
30 31
3 4
a
b
c
a
Interconnection cable (=main power supply)
b
Normal kWh rate power supply
c
Preferential power supply contact
2
Fix the cable with cable ties to the cable tie mountings.
INFORMATION
In case of preferential kWh rate power supply, connect
X6Y to X6YB. The necessity of separate normal kWh rate
power supply to indoor unit (b) X2M30/31 depends on the
type of preferential kWh rate power supply.
Separate connection to the indoor unit is required:
▪ if preferential kWh rate power supply is interrupted
when active, OR
▪ if no power consumption of the indoor unit is allowed at
the preferential kWh rate power supply when active.