11
|
Commissioning
Installer reference guide
240
ERGA04~08EA + EHBH/X04+08EF
Daikin Altherma 3 R W
4P629085-1B – 2021.11
2
Go to [A.3]:
Commissioning
>
Air purge
.
3
In the menu, set
Type
=
Manual
.
4
Select
Start air purge
.
5
Select
OK
to confirm.
Result:
The air purge starts. It stops automatically when ready.
6
During manual operation:
▪
You can change the pump speed.
▪
You must change the circuit.
To change these settings during the air purge, open the menu
and go to [A.3.1.5]:
Settings
.
▪
Scroll to
Circuit
and set it to
Space
/
Tank
.
▪
Scroll to
Pump speed
and set it to
Low
/
High
.
7
To stop the air purge manually:
—
1
Open the menu and go to
Stop air purge
.
2
Select
OK
to confirm.
To perform an automatic air purge
Conditions:
Make sure all operation is disabled. Go to [C]:
Operation
and turn off
Space heating/cooling
and
Tank
operation.
1
Set the user permission level to
Installer
—
2
Go to [A.3]:
Commissioning
>
Air purge
.
3
In the menu, set
Type
=
Automatic
.
4
Select
Start air purge
.
5
Select
OK
to confirm.
Result:
The air purge starts. It stops automatically when done.
6
To stop the air purge manually:
—
1
In the menu, go to
Stop air purge
.
2
Select
OK
to confirm.
11.4.3 Operation test run
Purpose
Perform test runs on the unit and monitor the leaving water and tank
temperatures to check if the unit is working correctly. The following test runs
should be made:
▪
Heating
▪
Cooling (if applicable)
▪
Tank