6
|
Application guidelines
Installer reference guide
55
ERLA11~W1 + EBVH16SU23DJ
Daikin Altherma 3 R F
4P655196-1 – 2021.09
▪
You can read out the energy data:
-
Per month
-
Per year
INFORMATION
The calculated produced heat and consumed energy are an estimation, the accuracy
cannot be guaranteed.
6.5.1 Produced heat
INFORMATION
The sensors used to calculate the produced heat are calibrated automatically.
▪
The produced heat is calculated internally based on:
-
The leaving and entering water temperature
-
The flow rate
▪
Setup and configuration: No additional equipment needed.
6.5.2 Consumed energy
You can use the following methods to determine the consumed energy:
▪
Calculating
▪
Measuring
INFORMATION
You cannot combine calculating the consumed energy (example: for backup heater)
and measuring the consumed energy (example: for outdoor unit). If you do so, the
energy data will be invalid.
Calculating the consumed energy
▪
The consumed energy is calculated internally based on:
-
The actual power input of the outdoor unit
-
The set capacity of the backup heater
-
The voltage
▪
Setup and configuration: To get accurate energy data, measure the capacity
(resistance measurement) and set the capacity via the user interface for the
backup heater (step 1).
Measuring the consumed energy
▪
Preferred method because of higher accuracy.
▪
Requires external power meters.
▪
Setup and configuration: When using electrical power meters, set the number of
pulses/kWh for each power meter via the user interface.
INFORMATION
When measuring the electrical power consumption, make sure ALL power input of
the system is covered by the electrical power meters.
Содержание Altherma 3 R F
Страница 309: ...13 13 ...
Страница 310: ......
Страница 311: ......
Страница 312: ...4P655196 1 2021 09 Copyright 2021 Daikin Verantwortung für Energie und Umwelt ...