10
|
Configuration
Installer reference guide
139
ERGA04~08EAV3(A) + 08S18+9W
Daikin Altherma 3 R F
4P629093-1 – 2020.08
If room buffering is enabled, the extra energy from photovoltaic panels is buffered
in the DHW tank and in the space heating circuit (i.e. heat up the room). With the
room comfort setpoints (cooling/heating) you can modify the maximum setpoints
that will be used when buffering the extra energy in the space heating circuit (i.e.
heat up the room).
#
Code
Description
[1.9.1]
[9-0A]
Heating comfort setpoint
▪
[3-07]~[3-06]°C
[1.9.2]
[9-0B]
Cooling comfort setpoint
▪
[3-09]~[3-08]°C
10.5.3 Main zone
Overview
The following items are listed in the submenu:
2
Main zone
Additional zone
Room
Malfunctioning
Space heating/cooling
[2]
Main zone
Setpoint screen
[2.1]
Schedule
[2.2]
Heating schedule
[2.3]
Cooling schedule
[2.4]
Setpoint mode
[2.5]
Heating WD curve
[2.6]
Cooling WD curve
[2.7]
Emitter type
[2.8]
Setpoint range
[2.9]
Control
[2.A]
Thermostat type
[2.B]
Delta T
[2.C]
Modulation
[2.D]
Shut off valve
[2.E]
WD curve type
Setpoint screen
Control the leaving water temperature for the main zone via setpoint screen [2]
Main zone
.
See
124].
Schedule
Indicate if the temperature of the leaving water is defined according to a schedule
or not.
Influence of the LWT setpoint mode [2.4] is as follows:
▪
In
Fixed
LWT setpoint mode, the scheduled actions consist of desired leaving
water temperatures, either preset or custom.
▪
In
Weather dependent
LWT setpoint mode, the scheduled actions consist of
desired shift actions, either preset or custom.
Содержание Altherma 3 R F EHVZ04S18E 6V Series
Страница 253: ......
Страница 254: ......
Страница 255: ......
Страница 256: ...4P629093 1 2020 08 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...