9.3.12 To connect the safety thermostat (normally closed contact)
Wires: 2×0.75 mm²
Maximum length: 50 m
Safety thermostat contact: 16 V DC detection (voltage supplied by PCB).
The voltage-free contact shall ensure the minimum applicable load of
15 V DC, 10 mA.
[9.8.1]=3 (
Benefit kWh power supply
=
Safety thermostat
)
1
"7.2.4 To open the indoor unit"
82]):
1
User interface panel
1
3
4
2
2
Switch box
3
Switch box cover
4
Top cover
2
Connect the safety thermostat (normally closed) cable to the appropriate
terminals as shown in the illustration below.
Note:
The jumper wire (factory-mounted) must be removed from the respective
terminals.
A
B
A
B
7 8
X 5M
1
8
Q4L
7
3
Fix the cable with cable ties to the cable tie mountings. General information,