10 Technical data
Installation manual
46
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598591-1A – 2019.12
10.3
Technical specifications: Domestic
hot water tank
10.3.1
Test results in accordance with EN12897
(2016)
Description
Test result
Hot water capacity
160 l
Reheat time
14 min
INFORMATION
This unit has been tested and approved according to
BS EN12897:2016
10.3.2
Warning label
WARNING TO USER
■ Do not remove or adjust any component part of this installation.
Contact the installer.
■ Should the system develop a fault, switch the system off and
contact the installer.
WARNING TO INSTALLER
■ This installation is subject to building regulation approval,
notify Local Authority of intention to install.
■ Use only manufacturer's recommended spare parts.
Contact your local Daikin dealer.
■ Installed by
name
address
tel. No.
completion date
TECHNICAL SPECIFICATIONS
EN12897: 2016
■ Maximum water supply pressure to pressure reducing valve:
16 bar
■ Operating pressure/set pressure of pressure reducing valve:
3.5 bar
■ Maximum primary working pressure (heating):
2.5 bar
■ Maximum flow temperature:
65
o
C
■ Expansion vessel pre-charge pressure:
3.5 bar
■ Expansion valve setting:
8 bar
■ Temperature and pressure relief valve
replacement part No.:
302810P
■ Operating pressure of temperature and pressure
relief valve:
10 bar
■ Operating temperature of temperature and pressure
relief valve:
95
o
C
■ Operating temperature of thermal cut-out (2 pieces):
89
o
C
■ Primary heating power input:
4.4 kW
■ Primary flow rate to reach primary heating power input:
15 l/min
■ Standing heat loss:
1.35 kWh/
24h
■ Storage capacity
180 l
■ Mass of unit when full
403 kg
■ Maximum design pressure:
10 bar
■ Rated volume heat exchanger:
9.1 l
4P599463-1A