6 Electrical installation
Installation manual
16
EGSAH/X06+10UD
Daikin Altherma 3 GEO
4P598591-1C – 2023.02
Item
Description
Room thermostat
(wired or wireless)
See:
▪ Installation manual of the room
thermostat (wired or wireless)
▪ Addendum
book
for
optional
equipment
Wires for wired room thermostat: (3
for cooling/heating operation; 2 for
heating only operation)×0.75 mm²
Wires for wireless room thermostat: (5
for cooling/heating operation; 4 for
heating only operation)×0.75 mm²
Maximum running current: 100 mA
For the main zone:
▪ [2.9]
Control
▪ [2.A]
Ext thermostat type
For the additional zone:
▪ [3.A]
Ext thermostat type
▪ [3.9] (read-only)
Control
Heat pump convector
See:
▪ Installation manual of the heat
pump convectors
▪ Addendum
book
for
optional
equipment
Wires: 4×0.75 mm²
Maximum running current: 100 mA
For the main zone:
▪ [2.9]
Control
▪ [2.A]
Ext thermostat type
For the additional zone:
▪ [3.A]
Ext thermostat type
▪ [3.9] (read-only)
Control
Remote indoor sensor
See:
▪ Installation manual of the remote
indoor sensor
▪ Addendum
book
for
optional
equipment
Wires: 2×0.75 mm²
[9.B.1]=2 (
External sensor
=
Room
)
[1.7]
Room sensor offset
Current sensors
See the installation manual of the
current sensors.
Wires: 3×2. Use part of the cable
(40 m) delivered as accessory.
[9.9.1]=3 (
Power consumption
control
=
Current sensor
)
[9.9.E]
Current sensor offset
Item
Description
Human Comfort
Interface
See:
▪ Installation and operation manual of
the Human Comfort Interface
▪ Addendum
book
for
optional
equipment
Wires: 2×(0.75~1.25 mm²)
Maximum length: 500 m
[2.9]
Control
[1.6]
Room sensor offset
6.4
To connect the main power supply
Use one of the following layouts to connect the power supply (for
details of C1~C5, see below the table):
#
Layout
Open the unit
(a)
1 Single cable power supply (= combined
power supply)
C1
C1
: Power supply for the backup heater,
and the rest of the unit (1N~ or 3N~)
Not necessary
(connection to
factory-mounted
cable outside of the
unit)
2 Dual cable power supply (= split power
supply)
Note:
This is for example needed for
installations in Germany.
C1
C5
C1
: Power supply for the backup heater
(1N~ or 3N~)
C5
: Power supply for the rest of the unit
(1N~)
4
3
2
1